![Tornatech GT-FluxFP Operating Instructions Manual Download Page 12](http://html.mh-extra.com/html/tornatech/gt-fluxfp/gt-fluxfp_operating-instructions-manual_1130758012.webp)
12
Tornatech - GT-FluxFP
TECHNICAL DATA
5
TECHNICAL DATA
Measuring principle
Orifice plate flowmeter with variable flowmeter
as indication
Input
»
Nominal Size
»
Pressure limit
»
Hydrostatically strength/
Pressure strength
2"/DN 50 grooved ends (Ø60.3 mm)
2½"/DN 65 grooved ends (Ø73.0 mm)
2½"/DN 65 grooved ends (Ø76.1 mm)
3"/DN 80 grooved ends (Ø88.9 mm)
4"/DN 100 grooved ends (Ø114.3 mm)
6"/DN 150 grooved ends (Ø165.1 mm)
6"/DN 150 grooved ends (Ø168.3 mm)
8"/DN 200 grooved ends (Ø219.1 mm)
10"/DN 250 grooved ends (Ø273.0 mm)
12"/DN 300 grooved ends (Ø323.9 mm)
PN 16 (232 psig)
64 bar (928 psig) for 5 min. (FM)
Measuring accuracy
±2.0 % of full scale value (FM)
Application conditions
»
Temperature limit
»
Medium
+4 °C to +50 °C (+39 °F to +122 °F)
Water
Design/ Material
»
Orifice plate
2"/DN 50 - 4"/DN 100
6"/DN 150 - 12"/DN 300
»
Differential pressure tube
»
Float
»
Bypass orifice
»
Filter
»
Seal
Housing tube in
stainless steel with turned grooved connection
coated steel with rolled grooved connection
1)
Brass
Stainless steel
Stainless steel
Stainless steel
NBR
Certifications
FM Approval 3056052