53
High Water Level
Put a jumper between High Water Level input and ground (See drawing for more details).
Water Reservoir Low
Put a jumper between Water Reservoir Low input and ground (See drawing for more details).
Pump Room Alarm
To activate this common alarm, at least one of the following alarms must be active: Low Fuel Level, High Fuel Level,
Fuel Tank Leak, AC Fail, Low Ambient Temperature, High Ambient Temperature, Low Suction Pressure, Water
Reservoir Empty, High Water Level or Water Reservoir Low.
Fail to Start
Disconnect #1, #9, #10 and #12 engine wires (See drawing for more details). Start the cranking sequence (Example:
Remove Remote Automatic Start jumper). Wait until the cranking sequence ends.
Overspeed
If your engine has an overspeed switch, switch it to the ON position. If not, disconnect #3 engine wire (See drawing
for more details) and put a jumper between #3 and #6. (Note: You don't need to start the engine to activate this
alarm.)
Electronic Control Module Selector Switch in Alternate Position (301)
Disconnect #301 engine wire. Put a jumper between #301 input and ground (See drawing for more details).
Fuel Injection Malfunction (302)
Disconnect #302 engine wire. Put a jumper between #302 input and ground (See drawing for more details).
Electronic Control Module Warning ( 303 )
Disconnect #303 engine wire. Put a jumper between #303 input and ground (See drawing for more details).
Electronic Control Module Fault ( 304 )
Disconnect #304 engine wire. Put a jumper between #304 input and ground (See drawing for more details).
Low Engine Temperature (312)
Disconnect #312 engine wire. Put a jumper between #312 input and ground (See drawing for more details).
Low Oil Pressure
Disconnect #4 engine wire (See drawing for more details). Put a jumper between #4 and ground. Start the engine.
High Engine Temperature
Disconnect #5 engine wire (See drawing for more details). Put a jumper between #5 and ground. Start the engine.
Battery 1 Failure
Disconnect #6 engine wire (See drawing for more details).
Battery 2 Failure
Disconnect #8 engine wire (See drawing for more details).
Weak Battery 1
You need to be logged in to modify these settings. Go to Config>Advanced>Alarms>WeakBattery1. Change the
Weak Battery 1 setpoint to the maximum allowable.
Weak Battery 2
You need to be logged in to modify these settings. Go to Config>Advanced>Alarms>WeakBattery2. Change the
Weak Battery2 setpoint to the maximum allowable.
Battery 1 Overvoltage
You need to be logged in to modify these settings. Go to Config>Advanced> Alarms>Battery1Overvoltage. Change
the Overvoltage Battery 1 setpoint to the minimum allowable.