TOPVERT L1 Series
E-
23
★
Pr5-05
Auto-tuning & control mode selection
0: No function
0
1: To execute auto-tuning and switch to
Sensor less vector control mode
2: Reset to V/F control mode
★
Pr5-06
Low Voltage Level l
230V models:
160
~
220VAC
460V models:
320
~
440VAC
230V:180
460V:360
★
Pr5-07
Over-Voltage Stall Prevention Level
230V models:
320
~
500VDC
460V models:
640
~
1000VDC
230V:380
460V:760
Pr5-08
Software Braking Level
230V models:
320
~
500VDC
460V models:
640
~
1000VDC
230V:373
460V:746
Pr5-09
Phase-Loss Protection
0: Warn and keep operation (below 50%)
0
1: Warn and ramp to stop
2: Warn and coast to stop
Pr5-10
Over- Current Stall Prevention level
during accel on the constant torque
region
Amp (10~250% of drive’s rated current)
A(170%)
Pr5-11
Over- Current Stall Prevention
low-limit level during accel on the
constant power region
Amp (0~250% of drive’s rated current)
A(120%)
Pr5-12
Over-Current Stall Prevention level
during constantan speed on the
constant torque region Operation
Amp (10~250% of drive’s rated current)
A(170%)
Pr5-13
Over- Current Stall Prevention
low-limit level during constant speed
run on the constant power region
Amp (0~250% of drive’s rated current)
A(120%)
Pr5-14
Over-Current Deceleration Time
during Operation
0.050~600.00 Sec
3.00
Pr5-15
Over-Torque Detection Selection 1
(ot1)
0
:
Disabled
0
1
:
Over-torque detection during constant
speed operation, stop operation after
detection.
2
:
Over-torque detection during constant
speed operation, continue to operate
after detection.
3
:
Over-torque detection during
operation, stop operation after
detection
4
:
Over-torque detection during
operation, continue operation after
detection.
Pr5-16
Over-Torque Detection Level 1 (ot1)
Amp(10
~
250% of drive’s rated current)
A (150%)
Pr5-17
Over-Torque Detection Time 1 (ot1)
0.0
~
60.0 Sec
0.1
Pr 5-18
Motor 1- Electronic Thermal Relay
Selection (oL1)
0
:
Electronic thermal relay function
disabled
0
1
:
Inverter duty motor
(with independent cooling fan)
2
:
Standard motor
(with shaft mounted cooling fan)
Pr5-19
Motor 1- Electronic Thermal Relay
Characteristic
30
~
600 Sec
60
Pr5-20
IGBT Over-Heat pre–warning setting
(oH2)
0.0~110.0
85.0
Pr5-21
Over-Torque Detection Selection 2
(ot2)
0: Disabled
0
1: Over-torque detection during constant
speed operation, stop operation after
detection.
2: Over-torque detection during constant
speed operation, continue to operate
after detection.
3: Over-torque detection during entire
(acceleration, steady state,