TopCold BC145V Instruction Manual Download Page 6

A3). 

7.2 Defrost 

1) d4=0, defrost is forbidden 

2) d4=1: 

    1. When evaporator sensor is enabled (d1=1), evaporator sensor temperature is higher than defrost 

termination temperature (d8), defrost could not be started. 

2. When evaporator  sensor  is  enabled  (d1=1),  evaporator  sensor  temperature  is lower  than  defrost 

termination temperature (d8), or evaporator sensor is disabled (d1=0), defrost could be started if any of 

the condition below is met: 

a. When defrost cycle d4) finishes running, start defrosting 

b. Hold and press key 

  for three seconds, start defrosting. 

3) Under defrost status, if any of the condition below is met, defrost could be closed: 

1. When evaporator sensor is enabled (d1=1), evaporator sensor temperature is higher than defrost 

termination temperature (d8), defrost is closed. 

2. Max. defrost time (d7) finishes running, defrost is closed. 

3. Hold and press key 

  for three seconds, close defrost. 

4) U3=00, K2 relay works as defrost relay output, and defrost method is electrical heating defrost. 

U3=01, at this time, no defrost relay and defrost method is off-cycle defrost. 

7.3 Lighting: 

U3=01: K2 relay works as lighting relay, press 

▲ to open the lighting and press ▲ key again to 

close the lighting. 

7.4 Alarm reminding 

When the cabinet temperature sensor failure, display E1 in digital tube; 

When the evaporator sensor failure, display E2 in digital tube. 

When the buzzer output selection 9A4) is 1, if the controller occurs alarm, the buzzer beeps; and 

when all alarm is relieved, buzzer mutes, or you could press any time to mute it. If new alarm occurs 

after relieving all alarm, buzzer will beep again.

 

 

Code 

Reason 

E1 

Cabinet temperature sensor failure 

E2 

Evaporator sensor failure 

H0 

one-key recovery failure 

dr 

one-key recovery success 

E2C 

Evaporator sensor disabled while display is selected    as 

evaporator sensor temperature   

8.  Wiring notice 

ACN,ACL  power  supply,  J2,J3  compressor  output,  J2,J4  defrost  output;  J6  cabinet 

temperature  sensor,  J5  evaporator  sensor;  the  ends  of  connection  cable  is  separately 

connected to power supply board    J7 and display panel J8. 

 

9. Safety rules: 

Summary of Contents for BC145V

Page 1: ...Refrigerators Freezers Instruction manual BC145V GK60 GN60 SD1381 SDN1381 PLEASE READ THE OPERATION MANUAL BEFORE USING SAVE THIS MANUAL FOR LATER USE ...

Page 2: ... all packaging away from children Dispose of the packaging in accordance with the regulations of local authorities If the power cord is damaged it must be replaced by a agent or a recommended qualified technician in order to avoid a hazard This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge un...

Page 3: ...2 2 123 158 4 others 6 2 4 Cabinet temperature control range 50 90 or 58 194 2 5 Power supply 220VAC 50 60Hz 2 6 Power consumption 3W 2 7 Output capacity Refrigeration 30A 240VAC normal open directly drive a single phase 1 5HP 220VAC load or optional 17A 240VAC normal open directly drive a single phase 1 0HP 220VAC load Defrost or lighting relay 10A 240VAC normal open directly drive heater strip M...

Page 4: ...e Press 3s to start forced defrost Exit from one key recovery status 5 2 Keys operation 6 2 1 Parameter adjustment In the status of temperature measuring and controlling press Set key for three seconds to enter user menu display St press Set key again display the parameter value of St then you could set temperature value by pressing or key When display St press key display Po press Set key display...

Page 5: ... key to execute the parameter recovery and then exit if there is no parameter recovery operation within 30S it will automatically exit from the mode without recovery of parameters Note It requires a reliable power supply during this operation or else you need to operate it again after power on the controller and get a reliable power supply H0 Give up parameter recovery no change of each parameter ...

Page 6: ...t and defrost method is electrical heating defrost U3 01 at this time no defrost relay and defrost method is off cycle defrost 7 3 Lighting U3 01 K2 relay works as lighting relay press to open the lighting and press key again to close the lighting 7 4 Alarm reminding When the cabinet temperature sensor failure display E1 in digital tube When the evaporator sensor failure display E2 in digital tube...

Page 7: ...oodstuffs in the appliance when it has reached the correct operating temperature Do not place uncovered hot food or liquid inside the appliance Wrap or cover food where possible Do not obstruct the fans inside the appliance Avoid opening the doors for prolonged periods of time Lock Unlock the Doors A lock is fitted to the doors to ensure foodstuffs are kept secure within your appliance Use the key...

Page 8: ...y Check doors are shut and seals are not damaged Appliance is located near a heat source or air flow to the condenser is being interrupted Move the refrigerator to a more suitable location Ambient temperature is too high Increase ventilation or move appliance to a cooler position Unsuitable foodstuffs are being stored in the appliance Remove any excessive hot foodstuffs or blockages to the fan App...

Page 9: ...oved and environmentally safe recycling process For further information on how to dispose of this product correctly contact the product supplier or the local authority responsible for waste disposal in your area Parts have undergone strict product testing in order to comply with regulatory standards and specifications set by international independent and federal authorities Products have been appr...

Reviews: