DME11D327-06
- 9 -
■
[
P 9 4
] Model Select
a) Press the temperature setting
▲ ▼ keys to select the system parameter
[
P 9 4
].
b) Press the START key
c) Press the time setting
▲ ▼ keys to set the model code.
d) Press the STOP key to return to the control panel display as shown below.
Press the STOP key again to end the procedures.
9. External Temperature sensor display adjustment [
c.12
]
1) Selecting Maintenance code [
C 12
]
2) Press the START key
(e.g., 23.42 degree C )
3) Press the START key while more than 2 seconds. It is displayed as shown below [r-1].
r- 1
0
C. 1 2
- - -
- -l
244
23.
42
Digital data (0-1023)
Temperature
0.01 degree C /unit
Temperature 1 degree C / unit
60.
P. 9 4
0
- -l
P. 9 4
1
- -l
Model Code
1 : SX-300/300E
2 : SX-500/500E
3: SX-700/700E
C. 1 0
- - -
- -l
P. 9 4
3
- -l
Model Code
3: SX-700/700E