4-5 Solenoid valve
The unit is operated by an electric signal from a remote
place in order to open or close an air supply valve.
Rc1/4
0.4~0.7MPa
-5~50°C
AC100/110V, AC200/220V, DC24V
50/60 Hz
AC: -10~10%, DC:-15~10%
G1/2 Conduit terminal
Double solenoid type and explosion-proof solenoid type are also available.
(1) Install the sub plate onto this product using the
sub-plate holding bolts and the two tapped holes
for solenoid valve installation located on the front
surface of this product. [Fig. 10]
(2) The solenoid valve installation orientation
depends on whether the valve is opened or
closed when energized. To reverse the orienta-
tion, remove the solenoid valve holding bolts,
reverse the solenoid valve orientation, and
re-install the unit [Fig. 11].
PCS2406-K090-Z03-132-
PCD2406-K090-Z04-120-
(The figure shows mounting orientation for "Energized to open").
Manufactured by KANEKO SANGYO
MK15G-8-
-DMI
MK15DG-8-
-DM
Energized to open
Sub-plate
holding bolt
Solenoid valve holding bolt
Standard specifications
Installation procedure
[Fig. 10]
[Fig. 11]
[Fig. 13]
[Fig. 14]
Standard specifications
(1) Fasten the attachment part set (plate) to the sub
plate with screws (short).
(2) Sandwich the attachment part (plate) and the filter
regulator with the attachment part (clamp).
(3) Fasten the attachment part (clamp) with screws
(long). [Fig. 12]
Installation procedure
P31EA22MMBNNP
Rc1/4
0.4~0.7MPa
Max 50°C
O-ring
Solenoid valve holding bolt
Attachment part set
[Fig. 12]
Solenoid valve unit
(non explosion-proof type)
Solenoid valve
(explosion-proof type)
(1) Install the solenoid valve unit to this product using
the solenoid valve holding bolts and the two
tapped holes for solenoid valve installation located
on cover 1 of this product. [Fig. 13]
(2) The solenoid valve installation orientation
depends on whether the valve is opened or closed
when energized. To reverse the orientation,
remove the solenoid valve holding bolts, reverse
the solenoid valve orientation, and re-install the
unit. [Fig. 14]
Installation procedure
O-ring
Energized
to close
Energized
to close
Drain exhaust port
Make sure to put the filter regulator drain exhaust port downwards.
O-ring
Plate
O-ring
Screws (short) (4pcs)
Screws (long) (2pcs)
Clamp
Pressure gauge
O-ring
For pressure-closing
single-acting type cylinders
(7F), "Energized to open"
is replaced with "Energized
to close" in the figure.
Sub plate
Table 3 Solenoid valve (non explosion-proof type) standard specifications
Port size
Operating pressure range
Ambient temperature
Rated voltage
Frequency
Allowable voltage fluctuation
Wiring method
Filter regulator
(direct installation)
Filter regulator (FR) can be directly fitted to the non
explosion-proof type solenoid valve unit.
FR is used to remove oil, moisture, and dust from
operating air (air filter) in order to protect pneumatic
equipment (solenoid valve, cylinder etc.), and to keep
appropriate constant operation pressure (regulator).
Table 4 Filter regulator standard specifications
Type
Port size
Operating pressure range
Ambient temperature
For pressure-closing single-acting
type cylinders (7F), "Energized to
open" is replaced with "Energized
to close" in the figure.
For double-acting/single-acting spring open
Tapped hole
Cover 1
⑥
Filter
regulator