7. List of models
TTM-339-□
□-□□□□□□
①
② ③
Symbol
Item
Description
Size
96 x 96
Input
Multi-input: Thermocouple, resistance temperature detector, voltage and current
①
OUT1 (Primary
control)
R
Relay contact output
P
SSR drive voltage output (0 to 12 VDC)
I
Current 4 to 20 mADC output
②
OUT2
(Primary/secondary
control)
N
None
R
Relay contact output
P
SSR drive voltage output (0 to 12 VDC)
I
Current 4 to 20 mADC output
③
Option
A
Relay contact outputs EV1 to EV3 *1
B
Relay contact output END signal output
C
Open collector outputs TS1 to 4, TIME, EV4 output *2
D
CT input *3
E
No-voltage contact input
M Communications RS-485
T English version panel sheet
*1
No EV3 if a relay contact output is selected for OUT1. No EV2 if a relay contact output is selected for OUT2.
*2
No EV4 if a relay contact output is selected for OUT1 or OUT2.
*3
Select I for OUT1 or OUT2. This CT is of a type to limit the operation amount but not to detect disconnection. It is
effective for the PID control of the heat control.
8. STANDARD SPECIFICATIONS
8.1 General specifications
Memory element
EEPROM
Input/Output isolation
Between Output area(control, event output) and Input area (process, CPU) and Power source
Power voltage
100 - 240 VAC, 50/60 Hz (Allowable voltage range: 85 - 110 %)
Power consumption TTM-339
10VA(AC264V)
Momentary power cut off
Within 1 cycle(20mS), Cut 100% power off on 100V AC at max. power consumption
Isolation resistance
Measurement terminal - case 500 VDC, 20 M
Ω
.
Power terminal - case 500 VDC, 20 M
Ω
.
Withstand voltage
Measurement terminal - case 1500 VAC for a minute.
Power terminal - case 500 VAC for a minute.
Operation
environment
Temperature
0
~
50
℃
Humidity
20 - 90 %RH (no dew condensation allowed)
Set angle
Datum surface
±
10 degrees
Vibration
0
~
0.2G
Transportation/sto
rage condition
Temperature
-20 - +70 °C (no freeze or dew condensation allowed)
Humidity
5 - 95 %RH (no dew condensation allowed)
8.2 Standard and performance
PV input area
Input type
Thermocouple
K,J,T,E,R,S,B,N,U,L,WRe5-26,PR40-20,PL
Ⅱ
switchable.
Effect of outer resistance approx.0.5
μ
V/
Ω
Indicating over, when wire is disconnected
R.T.D.
Pt100, JPt100 switchable
Allowable lead wire resistance 10
Ω
or less(per wire)
Indicating over, when wire is disconnected(for all of A, B and b)
Sampling time 0.2 sec. (same as output change frequency)
PV correct.
-199.9
~
999.9
℃
or -199
~
999
℃
Display/
Setting
Display type
PV/character
5-digit 7 segment LCD(back light colors of red, green and orange) letter height
20mm
Set value
5-digit 7 segment LCD(back light colors of red) letter height 8mm
Status
1-digit 6 segment LCD(back light colors of red)
Pattern display
2-digit 7 segment LCD(back light colors of green)