4.14.3-2 Primary/secondary control operation amount increase time
Setting items:
Primary/secondary control operation amount increase time: 0 to 3600 [second] (no function by setting at 0
[second])
Operation description:
For a remote run, apply a limit on the operation amount such that the ratio of the operation amount to the
calculated operation amount is from 0% at the start to 100% at the setting time.
The setting is effective also during AT.
If the setting is changed, control results change; redo the AT.
Operation is performed only at the control start (RDY to RUN or MAN or AT)
Care must be used, as no limit applies by the operation amount increase time after the setting time.
100%
Operation amount
Time
0
oHtM
Calculated operation amount
Limited operation amount
0%
oHtM
RDY
RUN
* No compensation applies
after the setting time.
Calculated operation
amount
Limited operation
amount
100%
100%
0%
0%
Time
4.15
Key lock
When a change of each parameter is attempted in a lock after lock ON/OFF is elected, “
LOC
” is displayed in the
SV display section.