- 21 -
h) Type of ERR
If there is an error in the message that was sent by the upper computer, the error number will
be included in the "response message" of this product for the reply.
Since error number "04" indicates the breakdown of measuring equipment (memory error, A/D
conversion error, or AT error), it will be included in the "response message" whether or not there
is an error in the "request message."
For multiple errors, the largest error number will be included.
Contents and classification of error are the following:
Error Number
Description of errors in the "request message" that was received by this product
01
Received an unsupported function code
02
Specified register address has no data
03
Numerical value data is out of the "setting range that is specified individually by the
setting item"
04
Malfunction of measuring equipment (memory error or A/D conversion error, AT error)