- 33 -
Iden-
tifier
Relative
Address
Absolute
Address
Charac-
ter
Name
R/W
Description
□MD
0028h 40041
Setting of Control Mode
R/W
R/W of the Setting of Control Mode
Execution of Control: 00000
Manual Control: 00001
Stop the Control: 00002
Auto Tuning is in Progress: 00003
CNT
002Ah 40043
Setting of Control Type
R/W
R/W of the Setting of Control Type
DIR
002Ch 40045
Switching of Direct
Action/Reverse Action
R/W
R/W of the Switching of Direct Action/Reverse
Action
MV1
002Eh 40047
Manipulated Variable of
Output 1
R/W
R/W of the Manipulated Variable of Output 1
TUN
0030h 40049
Setting of Tuning Type
R/W
R/W of the Setting of Tuning Type
ATG
0032h 40051
AT Coefficient
R/W
R/W of AT Coefficient
ATC
0034h 40053
AT Sensitivity
R/W
R/W of AT Sensitivity
□P1
0036h 40055
Setting of the Propor-
tional Band of Output 1
R/W
R/W of the Setting of the Proportional Band
of Output 1
□I1
0038h 40057
Setting of Integral Time
R/W
R/W of the Setting of Integral Time
□
D1
003Ah 40059
Setting of Derivative
Time
R/W
R/W of the Setting of Derivative Time
□T1
003Ch 40061
Setting of the Propor-
tional Cycle of Output 1
R/W
R/W of the Setting of the Proportional Cycle
of Output 1
ARW
003Eh 40063
Anti-Reset Windup
R/W
R/W of Anti-Reset Windup
MH1
0040h 40065
Maximum Limit of MV
Limiter
Settings
R/W
R/W of the Maximum Limit of MV Limiter
ML1
0042h 40067
Minimum Limit of MV
Limiter
Settings
R/W
R/W of the Minimum Limit of MV Limiter
□C1
0044h 40069
Setting of the Control
Sensitivity of Output 1
R/W
R/W of the Setting of the Control Sensitivity
of Output 1
CP1
0046h 40071
Setting of the OFF Point
of Output 1
R/W
R/W of the Setting of the OFF Point of Output
1
MV2
0048h 40073
Manipulated Variable of
Output 2
R/W
R/W of the Manipulated Variable of Output 2
□P2
004Ah 40075
Setting of the Propor-
tional Band of Output 2
R/W
R/W of the Setting of the Proportional Band
of Output 2
□T2
004Ch 40077
Setting of the Propor-
tional Cycle of Output 2
R/W
R/W of the Setting of the Proportional Cycle
of Output 2
MH2
004Eh 40079
Maximum Limit of MV
Limiter
Settings
R/W
R/W of the Maximum Limit of MV Limiter
ML2
0050h 40081
Minimum Limit of MV
Limiter
Settings
R/W
R/W of the Minimum Limit of MV Limiter
□C2
0052h 40083
Setting of the Control
Sensitivity of Output 2
R/W
R/W of the Setting of the Control Sensitivity
of Output 2
CP2
0054h 40085
Setting of the OFF Point
of Output 2
R/W
R/W of the Setting of the OFF Point of Output
2
PBB
0056h 40087
Manual Reset
R/W
R/W of the Manual Reset
□DB
0058h 40089
Setting of Dead Band
R/W
R/W of the Setting of Dead Band
RP1
005Ah 40091
Setting of SV Ramp Time
R/W
R/W of the Setting of SV Ramp Time
RP2
005Ch 40093
Setting of SV2 Ramp Time
R/W
R/W of the Setting of SV2 Ramp Time
EIF
005Eh 40095
PV Event Output 1
Function
Settings
R/W
R/W of the PV Event Output 1 Function
E1H
0060h 40097
Maximum Limit of Event
Output 1
Settings
R/W
R/W of the Maximum Limit of Event Output 1
E1L
0062h 40099
Minimum Limit of Event
Output 1
Settings
R/W
R/W of the Minimum Limit of Event Output 1