background image

Section 4 Maintenance and Troubleshooting

Maintenance

Maintenance Schedule

Engine Oil Recommendations

Engine Maintenance

Regular maintenance will improve performance and
extend engine/equipment life. BALDR INTERNATIONAL
LLC. recommends that all maintenance work be
performed by an Independent Authorized Service Dealer
(IASD). Regular maintenance, replacement or repair of
the emissions control devices and systems may be
performed by any repair shop or person of the owner’s
choosing. However, to obtain emissions control
warranty service free of charge, the work must be
performed by an IASD. See the emissions warranty.
NOTE: Call BALDR INTERNATIONAL LLC customer
service at +1 (855)801-0798 with questions about
component replacement.

Preventive Maintenance

Dirt or debris can cause improper operation
and equipment damage. Clean generator
daily or before each use. Keep area around
and behind muffler free from combustible
debris. Inspect all cooling air openings on
generator.

• Use a damp cloth to wipe exterior surfaces
clean.
• Use a soft bristle brush to loosen caked on
dirt, oil, etc.
• Use a vacuum to pick up loose dirt and
debris.
• Low pressure air (not to exceed 25 psi)
may be used to blow away dirt. Inspect
cooling air slots and openings on generator.
These openings must be kept clean and
unobstructed.

NOTE

: DO NOT use a garden hose to clean

generator. Water can enter engine fuel system
and cause problems. If water enters generator
through cooling air slots, some water will be
retained in voids and crevices of rotor and stator
winding insulation. Water and dirt buildup
on generator internal windings will decrease
insulation resistance of windings.

Follow maintenance schedule intervals,
whichever occurs first according to use.

NOTE

: Adverse conditions will require more

frequent service.

NOTE

: All required service and adjustments

should be each season as detailed in the following
chart.

To maintain the product warranty, the engine
oil should be serviced in accordance with the
recommendations of this manual. For your
convenience, maintenance kits designed and
intended for use on this product are available
from the manufacturer that include engine oil,
oil filter, air filter, spark plug(s), a shop towel
and funnel. These kits can be obtained from
an Independent Authorized Service Dealer
(IASD).

WARNING

Do not insert any object through the air cooling slots.
Generator can start at any time and could result in
death, serious injury, and unit damage.

WARNING

Accidental start-up. Disconnect spark plug wires when

working on unit. Failure to do so could result in death

or serious injury.

13

Owner’s Manual for Petrol Generator

At Each Use

Check engine oil level

Every 50 Hours

Clean Air Filter

Every 100 Hours or Every Season

Change Oil 

ǂ

Clean/Gap Spark Plug

Every 200 Hours or Every Season

Replace Air Filter
Replace Spark Plug
Check/Adjust Valve Clearance

ǂ

 Change oil after first 30 hours of operation,

then every season.

1.Change oil and oil filter every month when

operating under heavy load or in high tem-

peratures.

2.Clean more often under dirty or dusty oper-

ating conditions. Replace air filter parts if

they cannot be adequately cleaned.

3.Check valve clearance and adjust if neces-

sary after first 50 hours of operation and

every 300 hours thereafter.

Summary of Contents for GG8000

Page 1: ......

Page 2: ...Generator for Use Grounding the Generator When Used as a Portable 9 9 9 9 Maintenance Maintenance Schedule Preventive Maintenance Engine Maintenance Inspect Muffler and Spark Arrestor Valve Clearance...

Page 3: ...ccidents Adequate unobstructed flow of cooling and ventilating air is critical to correct generator operation Do not alter the installation or permit even partial blockage of ventilation provisions as...

Page 4: ...onoxide poisoning WARNING Moving Parts Keep clothing hair and appendages away from moving parts Failure to do so could result in death or serious injury WARNING Equipment and property damage Do not al...

Page 5: ...Accidental Start up Disconnect the negative battery cable then the positive battery cable when working on unit Failure to do so could result in death or serious injury WARNING Do not insert any object...

Page 6: ...Circuit Breaker AC 4 20 Amp Circuit Breaker AC 5 Hour Meter 6 OFF ON START Switch 7 Grounding 8 Fuel Tank 9 Battery 10 Oil Fill 11 Oil Drain 12 Recoil Starter 13 Air Filter 14 Choke Knob 15 Fuel Shut...

Page 7: ...injury TABLE 2 Product Specifications Generator Specifications Operating Temperature Range 18 deg C 0 deg F to 40 Deg C 104 Deg F When operated above 25 deg C 77 deg F there may be a decrease in powe...

Page 8: ...unlock Connect a suitable 4 wire grounded cord set to plug and desired load The cord set should be rated 250 Volts AC at 30 Amps or greater See Figure 2 5 Use this receptacle to operate 120 Volt AC 60...

Page 9: ...er for any missing carton contents 4 Record model serial number and date of purchase on front cover of this manual Figure 2 6 Wheel Foot Assembly WARNING Consult Manual Read and understand manual comp...

Page 10: ...ll cap and wipe dipstick clean See Figure 2 8 Figure 2 8 Remove Dipstick SAE 30 10W 30 Synthetic 5W 30 Figure 2 9 Safe Operating Range NOTE Some units have more than one oil fill location It is only n...

Page 11: ...y fuel level is correct 3 Verify unit is secure on level ground with proper clearance and is in a well ventilated area Prepare Generator for Use DANGER Asphyxiation Running engines produce carbon mono...

Page 12: ...found on a data label or decal affixed to the device If the appliance tool or motor does not give wattage multiply volts times ampere rating to determine watts volts x amps watts Some electric motors...

Page 13: ...ns and electrical output to that receptacle is lost Read Know Generator Limits carefully WARNING Recoil Hazard Recoil could retract unexpectedly Kickback could result in death or serious injury CAUTIO...

Page 14: ...NERATOR DOES NOT CHARGE THE BATTERY 1 Shut off all loads and unplug electrical loads from generator panel receptacles 2 Let engine run at no load for several minutes to stabilize internal temperatures...

Page 15: ...winding insulation Water and dirt buildup on generator internal windings will decrease insulation resistance of windings Follow maintenance schedule intervals whichever occurs first according to use N...

Page 16: ...p any spilled oil 10 Properly dispose of oil in accordance with all applicable regulations Engine will not run properly and may be damaged if run with a dirty air filter Service air filter more freque...

Page 17: ...negative battery terminal FIRST black wire 2 Disconnect positive battery terminal SECOND red wire NOTE The battery shipped with the generator has been fully charged A battery may lose some charge whe...

Page 18: ...e and run engine for long term storage Run engine for 10 15 minutes to circulate stabilizer throughout fuel system Adequately prepared fuel can be stored up to 24 months NOTE If fuel has not been trea...

Page 19: ...Bad spark plug 7 Water in fuel 8 Overchoking 9 Low oil level 10 Excessive rich fuel mixture 11 Intake valve stuck open or closed 12 Engine lost compression 1 Turn fuel shut off ON 2 Clean or replace...

Page 20: ......

Page 21: ......

Page 22: ...BALDR INTERNATIONAL LLC 322 Paseo Tesoro Walnut CA 91789 www togopower com 1 855 801 0798 Specifications are subject to change without notice...

Page 23: ...T CTANOS 1 855 801 0798 Lunes a viernes 8am a 5pm CST support togopower com www togopower com Tiene preguntas sobre el producto Necesitas soporte t cnico No dude en contactarnos en Lea atentamente el...

Page 24: ...generador cuando se utiliza como aparato port til 9 9 9 9 Mantenimiento Programa de mantenimiento Mantenimiento preventivo Mantenimiento del motor Inspect Muffler and Spark Arrester Holgura de la v l...

Page 25: ...cciones completamente Guarde estas instrucciones para referencia en el futuro SIEMPRE suministre este manual a la persona que usar la m quina NOTA Las notas contienen informaci n adicional importante...

Page 26: ...que podr a sufrir envenenamiento por mon xido de carbono ADVERTENCIA Piezas en movimiento Mantenga la ropa cabello y extremidades alejados de las piezas en movimiento No hacerlo puede ocasionar la mu...

Page 27: ...nque accidental Desconecte el cable negativo de la bater a luego el cable positivo de la bater a cuando trabaje en la unidad No hacerlo puede ocasionar la muerte o lesiones graves ADVERTENCIA No inser...

Page 28: ...ueo 3 Disyuntor de 27 amperios CA 4 Disyuntor de 20 amperios CA 5 Contador de horas 6 Interruptor OFF ON START 7 Toma de tierra 8 Dep sito de combustible 9 Bater a 10 Llenado de aceite 11 Drenaje del...

Page 29: ...mperatura de funcionamiento 18 C 0 F a 40 C 104 F Al funcionar a temperaturas mayores que 25 C 77 F puede haber una disminuci n de potencia La potencia y la corriente m ximas est n sujetas a y limitad...

Page 30: ...toma de corriente girar para bloquear desbloquear Conecte un cable de 4 conductores con conexi n a tierra al enchufe y a la carga deseada La capacidad nominal del cable deber a ser de 250 VCA con 30 a...

Page 31: ...atenci n al cliente de BALDR INTERNATIONAL LLC llamando al 1 855 801 0798 y cuando llame tenga a mano los n meros de modelo y serie 4 Escriba el n mero de modelo n mero de serie y fecha de compra que...

Page 32: ...nado de aceite est limpia 3 Retire la tapa de llenado de aceite y limpie la varilla de medici n Consulte la Figura 2 8 Figura 2 8 Sacar la varilla SAE 30 10W 30 5W 30 sint tico Intervalo de temperatur...

Page 33: ...ntes de arrancar el motor 1 Verifique si el nivel de aceite de motor es correcto 2 Verifique si el nivel de combustible es correcto 3 Verifique si la unidad est fija sobre terreno nivelado con separac...

Page 34: ...de datos pegados en el dispositivo Si el artefacto herramienta o motor no indica la potencia multiplique los voltios por amperios nominales para determinar los vatios V x A W Algunos motores el ctric...

Page 35: ...disyuntor se abre y se pierde la salida el ctrica a ese tomacorriente Lea atentamente Conozca los l mites del generador ADVERTENCIA Riesgo del arranque con cuerda El arranque con cuerda puede reaccion...

Page 36: ...GENERADOR NO CARGA EL BATER A 1 Apague todas las cargas y desenchufe las cargas el ctricas de los tomacorrientes del tablero del generador 2 Deje que el motor funcione sin carga durante varios minuto...

Page 37: ...s devanados internos del generador disminuir la resistencia del aislamiento de los devanados Respete los intervalos de mantenimiento programado el que ocurra primero acorde al uso NOTA Las condiciones...

Page 38: ...limpie el aceite que pueda haberse derramado 10 Deseche apropiadamente el aceite de El motor no funcionar correctamente y se puede da ar si lo usa con un filtro de aire sucio Efect e el servicio del...

Page 39: ...tale la buj a apretando con la mano y apriete 3 8 a 1 2 vuelta adicional usando una llave para buj as Figura 4 4 Buj a ADVERTENCIA Arranque accidental Desconecte el cable negativo de la bater a luego...

Page 40: ...ga funcionar el motor durante 10 15 minutos para hacer circular el estabilizador a trav s del sistema de combustible El combustible preparado adecuadamente se puede almacenar hasta 24 meses NOTA Si el...

Page 41: ...Soluci n de problemas 17 Manual de usuario para generador de gasolina...

Page 42: ...18 Manual de usuario para generador de gasolina...

Page 43: ......

Page 44: ...BALDR INTERNATIONAL LLC 322 Paseo Tesoro Walnut CA 91789 www togopower com 1 855 801 0798 Las especificaciones est n sujetas a cambios sin aviso...

Reviews: