9. Connection

Wiring

Take care that earth terminal "E" will be connected to earth.

Make sure to connect the frame ground terminal at the rear side to ground.

1

2

3

4

Earth

9.1. Terminal plug connection 

Step 1. Strip a cable jacket of approx. 7 mm from the cable end.  

For cables, refer to 

p. 10

, type of cable. 

Note 

Do not solder plate on exposed inner cables when using a stran-

ded wire.  

Step 2. Loosen the terminal screws and insert the cables.  
Step 3. Tighten the terminal screws securely. 

Notes 

• Tug lightly on the cable to be sure that it does not pull free. If the cable pulls free, loosen the terminal 

screw again and reconnect from Step 2.  

• Use the screwdriver appropriate to the screws tightened into the terminal plug.  

Step 4. (Removable terminal plug only)  

Insert the wired terminal plug into the terminal block or the pin header.  

Connector

Tighten  

Terminal block  

Removable terminal plug   (sup-

plied with the RS-410EC)  

G   1 2 3 4 E

Ground

Summary of Contents for RS-410EC e

Page 1: ...com Station Please carefully follow the instructions in this manual to ensure long trouble free use of your equipment Note For operation of the units refer to the N 8000 series operating instructions...

Page 2: ...ng be sure to grasp the plug never pull on the cord itself Operating the unit with a damaged cord may cause a fire or electric shock Avoid installing the unit in dusty locations or in locations expose...

Page 3: ...ded for informational calls It features 2 different programable call targets each one individual target per button Emergency calls are listed in position one of the call queue on the master station N...

Page 4: ...exchange 4 Emergency Push Button The button is protected by a protective pane In case of emergency this pane has to be smashed 5 Standard Push button Used to call the pre programmed master station Se...

Page 5: ...sing of a button does not direct the call to another station After the call has been proceeded and finished a new call can be processed A smashed pane is to be replaced by a new pane spare part 7 1 2...

Page 6: ...tions where it gets splashed with water Recommended Back Boxes for RS 410EC are either for flush mounting IW 101 or for surface mounting OW 101 Provide a weep hole at the bottom of the mounting box to...

Page 7: ...sing a stran ded wire Step 2 Loosen the terminal screws and insert the cables Step 3 Tighten the terminal screws securely Notes Tug lightly on the cable to be sure that it does not pull free If the ca...

Page 8: ...be registered via the Model Name RS 442 The system mode shall be Selective Response 10 1 Programming the LED of emergency push button lit if the emergency button was pressed Activate Calling Station I...

Page 9: ...DIMENSIONAL DIAGRAM Unit mm FRONT VIEW BOTTOM VIEW RS 410EC e Priority Call 1 1 low priority Call 2 5 emergency call high priority Call 3 Not available Call Master Call 1 Call Target for Standard Pus...

Page 10: ...ve pane Operation Indicator 1 LED Wiring Twisted pair cables 2x pair Transmission Range 1km 0 5mm AWG24 1 5km 0 65mm AWG22 2km 0 9mm AWG19 Installation Method Flush mount Surface mount Housing Protect...

Reviews: