TMK JOKER DS2PM-RC Instruction And Installation Manual Download Page 9

MENU OF VALVE PARAMETERS – group

 E

In order to modify valve parameters, press the [MENU] button. A list of groups of parameters will appear on 
screen. Turn the knob right (clockwise) to select the 

E

 group  - “Valve”. Press [SELECT] or the knob. “

E

1”, 

the first parameter from the valve group will be displayed. To go to different parameters, turn the knob right, 
and then press the [EDIT] / [SELECT] button or the knob to change a desired parameter. Now you can 
change the value of the parameter using the knob or the dynamically alternating buttons. 
Some parameters need to be selected for editing: use the SELECT button and the knob

.

To save changes, press the [SAVE] button or press the knob. 
The [EXIT] button restores the previous menu level without saving changes.

LIST OF VALVE PARAMETERS

 (to switch parameters and change setting – turn the knob):

E1 

 M

aximal temperature behind

 the

 valve

 (s

etting maximal temperature behind valve E1a, E1b or E1c below 

corresponding E2a, E2b or E2c 

[

minimal temp. behind valve

]

 results in both settings becoming equal

)

  

E1a day (1-99°C, default: 45°C)
E1b night (1-99°C, default 30°C)
E1c economy (1-99°C, default: 25°C)

E2 

 Min

imal temperature behind

 the

 valve

(s

etting minimal temperature behind valve E2a, E2b or E2c above 

the corresponding E1a, E1b or E1c [max temp. behind valve] results in both settings becoming equal

)

E2a day (1-99°C, default: 35°C)
E2b night (1-99°C, default 20°C)
E2c economy (1-99°C, default: 15°C)

E3  Minimal temperature of the boiler return pipe regulated by the valve 

(

40

-

55

°C, default: 5

0

°C)

E4  

Valve downtime (valve action time is constant - 1 sec.) (0-200 sec., default setting: 10 sec.)

E5  

Manual valve mode (the [STOP] button switches off the manual mode)

E

6

 

 

Direction of valve turning (press [EDIT] and confirm to reverse direction of turning of the valve

)

CAUTION: return to default settings will not change direction of valve turning

.

 

When boiler temperature at the return is lower than parameter E3, the valve is closed. When temperature at 

the return is equal to the E3 setting, the valve remains closed. The controller allows to open the valve only 
when temperature at the return is higher than the E3 setting.

Over the first 6 hours after the FIRE UP precedure has been started the controller does not take into account 

the minimal temperature at the return to the boiler.

When hot water tank priority has been selected (parameter F3 set to "YES"), over the first 3 hours from 
switching on the C.H. pump the controller does not take into account the minimal temperature at the return to 
the boiler. 

9

Press

MENU

pressing the knob or 

the [SELECT] button

Turn the knob

to select

V

alve

Summary of Contents for JOKER DS2PM-RC

Page 1: ...ed spaces is maintained at desired levels while the boiler operates in optimal conditions ensuring increased life expectancy The user can limit the number of controlled appliances thanks to flexible c...

Page 2: ...power supply Otherwise the pump may become damaged General technical data Supply voltage 230V 50Hz Maximum pump output 3x100VA 1x250VA stoker 1x5VA valve Anti stop function pump protection against jam...

Page 3: ...IN SCREEN START STOP manual mode current temperature of the boiler Turn the knob to set blower speed arrows are flashing 1 Installation of the boiler temperature sensor and thermal breaker switch Fix...

Page 4: ...t 6 hours from switching from the SUMMER mode to the WINTER mode the controller does not take into account the minimal temperature at the return to the boiler parameter E3 ALERTS The controller featur...

Page 5: ...45 C Boiler extinguish temperature cannot be higher than the difference of parameters A1 minus A2 minus 5 C A4 Fire up duration 10 480 min default 6 hours A5 low boiler temperature alert 0 50 C defau...

Page 6: ...the knob or using the dynamically appearing buttons Editing is confirmed by pressing the knob or the SAVE button Pressing EXIT will bring back the previous screen without saving any changes LIST OF P...

Page 7: ...o change parameters of the C H pump List of groups of parameters will appear on the screen Turn the knob right clockwise to select group D C H pump and then to select press the knob or the SELECT butt...

Page 8: ...ehind valve is programmable different temperatures can be set for every day and hour of the week parameter H1 The central heating timed programme in use is displayed on the MAIN SCREEN between the CH...

Page 9: ...valve E2a E2b or E2c above the corresponding E1a E1b or E1c max temp behind valve results in both settings becoming equal E2a day 1 99 C default 35 C E2b night 1 99 C default 20 C E2c economy 1 99 C d...

Page 10: ...on if 1 the set temperature of domestic hot water has not been achieved and 2 when the temperature at the C H boiler is higher than that inside of the hot water tank by the parameter F4 protection of...

Page 11: ...take into account the minimal temperature at the return to the boiler parameter E3 F4 DHW tank protection from cooling down 0 15 C default setting 5 C F5 Minimal temperature of the CH boiler at which...

Page 12: ...l temperature behind valve is edited H high means that room temperature has not been reached and maximal temperature behind valve is edited Pressing the or button again will further increase or decrea...

Page 13: ...If NO has been selected oker controller operation with is deactivated LIST OF ROOM PANEL PARAMETERS G1 Room temperatures G2 Precision of room temperature control hysteresis 0 1 0 5 C default setting 0...

Page 14: ...elected day to another day of the week which you select with the knob Press SELECT or the knob Press EDIT or the knob In this screen turn the knob to select time interval to be edited Press NEXT or th...

Page 15: ...of coal consumption COAL CONSUMPTION PARAMETER MENU group I COAL CONSUMPTION SETTINGS CAUTION It is advisable to verify the estimation of coal consumption performed by the controller from time to time...

Page 16: ...zech CAUTION Return to default settings does not concern language K8 Information about the controller model software version 5 1 6 0 read only K9 Contrast of the display 1 31 default setting 12 CAUTIO...

Page 17: ...r defects which can be attributed to the manufacturer TMK sp j shall repair or replace the faulty controller with a defect free device within 14 working days from the date of returning the controller...

Reviews: