TMK JOKER DS2PM-RC Instruction And Installation Manual Download Page 3

C.H. HEATING BOILER CONTROL (OF THE BLOWER AND STOKER)

Installation

MANUAL MODE OF THE STOKER AND BLOWER

The user can flexibly switch on and off the stoker as well as the blower. It may useful for instance when the 
boiler is ignited with empty stoker. 

The screen "Manual mode of the stoker and blower" is available on pressing [MODE], and then within five 
seconds [MANUAL MODE].

 

The manual mode screen is available alternatively under parameters B4 and 

C

8

.

FIRING UP OF THE BOILER WITH EMPTY STOKER

After the coal container is filled, switch on the stoker by pressing [START stoker] until coal appears in the 
retort. 

Then switch off the stoker by pressing [STOP stoker], and ignite coal in the retort. Next, switch on the 
blower [START blower] and set its optimal speed by turning the knob (current blower speed is displayed on 
the screen in per cent)

.

 
When coal in the retort has been ignited switch to automatic mode -  press [EXIT] and then [START] on the 
main screen. Automatic mode is described on page 4.

Screen of the MANUAL MODE OF THE STOKER AND BLOWER

:

3

Animated movement of the helix means that the stoker is feeding coal. 

CAUTION - the controller does not automatically return from "Manual mode of the stoker and blower" 
menus to the MAIN SCREEN

.

 .

START / STOP 

manual mode

current temperature 

of the boiler

Turn the knob

to set blower speed

(arrows are flashing)

1. 

Installation of the boiler temperature sensor and thermal breaker switch

Fix the sensor and thermal breaker switch to an uninsulated exit pipe of the C.H. boiler with two provided strips so 
that they adhere well.

It is recommended to additionally wrap the sensor and thermal breaker switch with some thermal insulation 
material.

2. 

Installation of the 

stoker

 temperature sensor

The stoker sensor must be fixed to the feeding pipe where designated by the boiler producer.

If the boiler producer provided no instructions, for best results install the sensor on the feeding pipe 50 cm from where 
coal enters the furnace.

Attach the sensor to the pipe with the provided metal strap so that it adheres well.

CAUTION: Incorrect installation may damage the sensor.
CAUTION: The sensor 

and thermal breaker switch

 are not made for direct use in water.

3. 

Connecting the power cord to the blower

 and the stoker

ź

Connect the yellow-green wire (zero protection) to the marked terminal of the blower

/stoker

.

ź

Connect brown and blue wires to L and N terminals of the blower

/stoker

.

ź

in case of the version with IEC connector, plug in the controller and the blower

/stoker

CAUTION: The regulator must be installed by a qualified electrician only.

current temperature 

of the 

stok

er

current temperature 

of the boiler

 return

Summary of Contents for JOKER DS2PM-RC

Page 1: ...ed spaces is maintained at desired levels while the boiler operates in optimal conditions ensuring increased life expectancy The user can limit the number of controlled appliances thanks to flexible c...

Page 2: ...power supply Otherwise the pump may become damaged General technical data Supply voltage 230V 50Hz Maximum pump output 3x100VA 1x250VA stoker 1x5VA valve Anti stop function pump protection against jam...

Page 3: ...IN SCREEN START STOP manual mode current temperature of the boiler Turn the knob to set blower speed arrows are flashing 1 Installation of the boiler temperature sensor and thermal breaker switch Fix...

Page 4: ...t 6 hours from switching from the SUMMER mode to the WINTER mode the controller does not take into account the minimal temperature at the return to the boiler parameter E3 ALERTS The controller featur...

Page 5: ...45 C Boiler extinguish temperature cannot be higher than the difference of parameters A1 minus A2 minus 5 C A4 Fire up duration 10 480 min default 6 hours A5 low boiler temperature alert 0 50 C defau...

Page 6: ...the knob or using the dynamically appearing buttons Editing is confirmed by pressing the knob or the SAVE button Pressing EXIT will bring back the previous screen without saving any changes LIST OF P...

Page 7: ...o change parameters of the C H pump List of groups of parameters will appear on the screen Turn the knob right clockwise to select group D C H pump and then to select press the knob or the SELECT butt...

Page 8: ...ehind valve is programmable different temperatures can be set for every day and hour of the week parameter H1 The central heating timed programme in use is displayed on the MAIN SCREEN between the CH...

Page 9: ...valve E2a E2b or E2c above the corresponding E1a E1b or E1c max temp behind valve results in both settings becoming equal E2a day 1 99 C default 35 C E2b night 1 99 C default 20 C E2c economy 1 99 C d...

Page 10: ...on if 1 the set temperature of domestic hot water has not been achieved and 2 when the temperature at the C H boiler is higher than that inside of the hot water tank by the parameter F4 protection of...

Page 11: ...take into account the minimal temperature at the return to the boiler parameter E3 F4 DHW tank protection from cooling down 0 15 C default setting 5 C F5 Minimal temperature of the CH boiler at which...

Page 12: ...l temperature behind valve is edited H high means that room temperature has not been reached and maximal temperature behind valve is edited Pressing the or button again will further increase or decrea...

Page 13: ...If NO has been selected oker controller operation with is deactivated LIST OF ROOM PANEL PARAMETERS G1 Room temperatures G2 Precision of room temperature control hysteresis 0 1 0 5 C default setting 0...

Page 14: ...elected day to another day of the week which you select with the knob Press SELECT or the knob Press EDIT or the knob In this screen turn the knob to select time interval to be edited Press NEXT or th...

Page 15: ...of coal consumption COAL CONSUMPTION PARAMETER MENU group I COAL CONSUMPTION SETTINGS CAUTION It is advisable to verify the estimation of coal consumption performed by the controller from time to time...

Page 16: ...zech CAUTION Return to default settings does not concern language K8 Information about the controller model software version 5 1 6 0 read only K9 Contrast of the display 1 31 default setting 12 CAUTIO...

Page 17: ...r defects which can be attributed to the manufacturer TMK sp j shall repair or replace the faulty controller with a defect free device within 14 working days from the date of returning the controller...

Reviews: