![TMEIC PVU-L0800GR Installation Manual Download Page 43](http://html1.mh-extra.com/html/tmeic/pvu-l0800gr/pvu-l0800gr_installation-manual_1121785043.webp)
4GBG1009
PVU-L0800GR / PVU-L0840GR / PVU-L0880GR Installation Manual
42
Table 16.5
Utility interconnection voltage and frequency trip limits and trip times
(
PVU-L0800GR / PVU-L0840GR / PVU-L0880GR
)
Condition
Voltage (V)
Frequency (Hz)
Trip time (sec)
A
V≥120% Vnor
(Default)
105%Vnor≤ V< 140% Vnor
(Adjustable)
Rated
0.16 sec (Default)
(Adj. 0.010s to 65s)
B
110%Vnor≤ V< 120% Vnor
(Default)
105%Vnor≤ V< 140% Vnor
(Adjustable)
Rated
13 sec (Default)
(Adj. 0.010s to 65s)
C
70%Vnor≤ V< 88% Vnor
(Default)
10%Vnor≤ V< 95% Vnor
(Adjustable)
Rated
21 sec (Default)
(Adj. 0.010s to 65s)
D
50%Vnor≤ V< 70% Vnor
(Default)
10%Vnor≤ V< 95% Vnor
(Adjustable)
Rated
11 sec (Default)
(Adj. 0.010s to 65s)
E
V< 50% Vnor
(Default)
10%Vnor≤ V< 95% Vnor
(Adjustable)
Rated
1.5 sec (Default)
(Adj. 0.010s to 65s)
F
Rated
> 62 Hz (Default)
60.1 Hz to 65.0 Hz
(Adjustable)
* tested up to 64Hz
0.16 sec (Default)
(Adj. 0.010s to 655s)
G
Rated
< 60.5 Hz (Default)
60.1 Hz to 65.0 Hz
(Adjustable)
* tested up to 64Hz
300 sec (Default)
(Adj. 0.010s to 655s)
H
Rated
< 58.5Hz (Default)
59.9 Hz to 53.0 Hz
(Adjustable)
300 sec (Default)
(Adj. 0.010s to 655s)
I
Rated
< 57.0Hz (Default)
59.9 Hz to 53.0 Hz
(Adjustable)
0.16 sec (Default)
(Adj. 0.010s to 655s)
Reconnection time setting is at 300s default, but has field adjustable settings from 7s to 600s.
17. Contact
For technical inquires, order of spare parts or repairs, please contact your local TMEIC sales or service
representative.