2.6. Installation and wiring of the inverter
■
During installation, do not incline the inverter at angles more than 10°
If the inverter is inclined at angles more than 10°, it may fall causing injuries and/or
damage.
■
The inverter must be connected to ground
Ground the inverter through the terminal marked “Grounding Electrode Terminal”.
If not grounded, insulation degradation may cause current leakage and create a
risk of electric shock.
Ensure a ground resistance of less than 5Ω.
■
The input and output circuits are isolated from the enclosure. Is the responsibility of the
installer to provide for system grounding in case it is required by sections 690-40 and 690-42
of the National Electric Code, ANSI/NFPA 70.
■
The AC output is not connected to ground
Do not ground any AC conductor. If the inverter is connected to a wye connected transformer, do not
ground the neutral of the wye connection.
■
Wiring methods in accordance with the National Electrical Code, ANSI/NFPA 70 are to be used.
■
After completing the installation and wiring work, make sure that all
protective covers are put in place
There is a risk of electric shock and injury if protective covers are not installed.
DANGER
Forbidden
Grounding Electrode
Terminal
Mandatory