172-65129A-03 (GAS1N/GAS2N/GAS3N) 23 Oct 2018
9
Installation
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
Use hoisting equipment for heavy objects (weighing approximately
20 kg (44 lb) or more). Failure to do so may result in back strain or other
injury if the object should fall.
CAUTION
Take measures to prevent people from coming into direct contact with
product outlets. Failure to do so may result in burns or other injury from
the discharge of fluids.
CAUTION
Installation, inspection, maintenance, repairs, disassembly, adjustment and valve
opening/closing should be carried out only by trained maintenance personnel.
1. Before installation, be sure to remove all protective seals.
2. Before installing the product, open the inlet valve and blow out the piping to
remove any piping scraps, dirt and oil. Close the inlet valve after blowdown.
3. Install the product so that the arrow on the body is pointing in the direction of
flow.
4. The product should be installed within the allowable angles of inclination,
shown below.
5. Install a condensate outlet valve and outlet piping.
6. To ensure proper condensate flow into the trap, install a pressure-balancing
line. Remove holder rod and its associated parts (see “Configuration”) and
connect the pressure-balancing line. Connect the opposite end of the
pressure-balancing line to the air/gas main or an air/gas space above any
possible condensate accumulation in the system. For more details, see the
section “The Need for a Pressure-balancing Line”.
7. Open the inlet and outlet valves and check to make sure that the product
functions properly.
If there is a problem, determine the cause using the “Troubleshooting” section in
this manual.
Tolerance Angles for Installation
The product should be installed so that the letters
on the trap are horizontal.