172-65762M-00 (EF200W-C Vortex flowmeter)  8 February 2021

EF200W-C

Vortex flowmeter

Copyright © 2021 by TLV CO., LTD.

All rights reserved

Summary of Contents for EF200W-C

Page 1: ...172 65762M 00 EF200W C Vortex owmeter 8 February 2021 EF200W C Vortex owmeter Copyright 2021 by TLV CO LTD All rights reserved...

Page 2: ...cation Orientation Inlet and outlet runs Mounting kit for disc wafer version Length of connecting cable Mounting the transmitter housing Environment Ambient temperature range Storage temperature Clima...

Page 3: ...evice Inner ground terminal Connects the protectiv earth to the mains supply Outer ground terminal Connects the device to the plant grounding system Symbols for certain types of information Symbol Mea...

Page 4: ...endent of the ow velocity and the uid properties viscosity and density Independent of the type of substance under measurement steam gas or liquid The primary measuring signal is linear to the ow After...

Page 5: ...such as in most water and steam applications The measuring device does not display an o set in the calibration and the accuracy is still guaranteed All the edges on the blu body have a radius that is...

Page 6: ...ia four line Via operating tools A0013471 Sensor EF200W C Disc wafer version Nominal diameter range DN 15 to 150 to 6 Materials Measuring tubes stainless steel CF3M 1 4408 A0009922 Input Measured vari...

Page 7: ...nal restrictions apply to both the lower range value and the upper range value Flow measuring ranges in SI units DN mm Liquids m h Gas steam m h 15 0 06 to 4 9 0 3 to 25 25 0 18 to 15 0 9 to 130 40 0...

Page 8: ...nolds number is dimensionless and indicates the ratio of the inertia force of a uid to its viscous force when owing and is used as a characteristic variable for pipe ows In the case of pipe ows with R...

Page 9: ...vibrations present a The value mf corresponds to the lowest measurable ow velocity without vibration no wet steam at a density of 1 kg m3 0 0624 lbm ft 3 The value mf can be set in the range from 6 t...

Page 10: ...ensure that the signals can be evaluated without error This results in a maximum permitted ow rate QAmpMax Q m h AmpMax 350 m s D m i 3600 s h 4 m g k m g k 1 Q min AmpMax 1148 s D ft i 60 s min 4 0...

Page 11: ...QHigh is determined using the smallest of the three values Qmax QAmpMax and QMa 0 3 Q m h min High Q m h max Q m h AmpMax Q m h Ma 0 3 High Q min max Q min AmpMax Q min Ma 0 3 A0034338 QHigh E ective...

Page 12: ...collector Maximum input values DC 35 V 50 mA Voltage drop For 2 mA 2 V For 10 mA 8 V Residual current 0 05 mA Pulse output Pulse width Adjustable 5 to 2 000 ms Maximum pulse rate 100 Impulse s Pulse v...

Page 13: ...atus Status of low ow cut o Signal on alarm Depending on the interface failure information is displayed as follows Current output 4 to 20 mA 4 to 20 mA Failure mode Choose from 4 to 20 mA in accordanc...

Page 14: ...ending on the external supply voltage of the power supply unit Calculation of the maximum load Depending on the supply voltage of the power supply unit US the maximum load RB including line resistance...

Page 15: ...more information HART load Min 250 Max 500 Power supply Terminal assignment Transmitter Connection versions 3 4 1 2 C A B A0033475 Maximum number of terminals Terminals 1 to 4 Without integrated over...

Page 16: ...nals are always used to connect the connecting cable in the sensor connection housing tightening torques for screws for cable strain relief 1 2 to 1 7 Nm Connecting cable 2 1 1 2 1 2 3 4 1 2 3 4 GN YE...

Page 17: ...following table 3 Voltage drop 2 2 to 3 V for 3 59 to 22 mA Increase in minimum terminal voltage Display operation Increase in minimum terminal voltage Local operation DC 1 V Power consumption Transm...

Page 18: ...tored Electrical connection Connecting the transmitter 1 1 A0033480 1 Cable entries for inputs outputs Remote version connection Connecting cable 3 1 2 A0033481 Connecting cable connection 1 Wall hold...

Page 19: ...o comply with EMC requirements observe cable speci cations 4 Analog display unit observe maximum load 5 Transmitter Pulse frequency output 1 2 3 12345 A0028761 Connection example for pulse frequency o...

Page 20: ...tallation guidelines that apply in the country of installation must be observed The cables must be suitable for the minimum and maximum temperatures to be expected Signal cable Current output 4 to 20...

Page 21: ...charge current 8 20 s 10 kA Temperature range 40 to 85 C 40 to 185 F 1 The voltage is reduced by the amount of the internal resistance Imin Ri Performance characteristics Reference operating condition...

Page 22: ...ange Maximum measured error Standard 20 to 50 66 to 164 150 302 or 423 K Re2 to Remax A1 1 7 Re1 to Re2 A2 10 10 to 70 33 to 210 140 284 or 413 K Re2 to Remax A1 2 Re1 to Re2 A2 10 10 33 Re Re1 A2 A1...

Page 23: ...mismatch between the device ange e g ASME B16 5 Sch 80 DN 50 2 and the mating pipe e g ASME B16 5 Sch 40 DN 50 2 Only apply diameter mismatch correction within the following limit values listed below...

Page 24: ...is the average vortex period duration of the owing uid Influence of ambient temperature Current output o r of reading Additional error in relation to the span of 16 mA Temperature coe cient at zero po...

Page 25: ...tation transmitter head down A0015590 4 D Horizontal orientation transmitter head at side A0015592 1 In the case of liquids there should be upward ow in vertical pipes to avoid partial pipe lling Fig...

Page 26: ...DN 40 1 for spacing see graphic If there are several ow disturbances present the longest speci ed inlet run must be maintained If the required inlet runs cannot be observed it is possible to install a...

Page 27: ...outlet runs with various ow obstructions 1 3 4 2 5 6 7 5 DN 8 Flow conditioner 9 h Flow conditioner Flow conditioner Flow conditioner Flow conditioner Flow conditioner Flow conditioner Flow condition...

Page 28: ...ie rods Seals Nuts Washers 1 2 3 A0019875 Mounting kit for wafer version 1 Nut washer tie rod 2 Seal 3 Centering ring is supplied with the measuring device Length of connecting cable To ensure correct...

Page 29: ...EF200W C 29 Mounting the transmitter housing Wall mounting 80 3 15 5 1 3 0 8 19 0 6 M8 A0033484 Post mounting 20 70 1 4 x SW 13 A0033486 mm in 1 Mounting kit for post mounting mm in...

Page 30: ...weather protection cover from TLV Storage temperature 50 to 80 C 58 to 176 F Climate class DIN EN 60068 2 38 test Z AD Degree of protection Transmitter As standard IP66 67 type 4X enclosure When housi...

Page 31: ...rature The pressure temperature rating for the speci c measuring device is programmed into the software If values exceed the curve range a warning is displayed Depending on the system con guration and...

Page 32: ...el CF3M 1 4408 Wafer flange for connection to flanges according to JIS B2220 0 10 20 30 40 50 60 200 100 0 100 200 300 400 C F bar psi 0 100 200 300 400 500 600 700 800 900 400 200 0 800 200 600 400 2...

Page 33: ...A wide range of materials can be used for the required insulation This applies for Compact version Remote sensor version The maximum insulation height permitted is illustrated in the diagram 1 A001921...

Page 34: ...32 4 262 0 294 4 159 9 58 2 101 7 27 6 65 64 40 4 140 2 51 7 88 5 41 5 270 5 312 0 159 9 58 2 101 7 42 65 82 50 140 2 51 7 88 5 46 5 277 5 324 0 159 9 58 2 101 7 53 5 65 92 80 140 2 51 7 88 5 64 0 29...

Page 35: ...G Q Q F T A0033796 A 1 B C1 F 2 G3 Q T 3 mm mm mm mm mm mm mm 140 2 51 7 88 5 254 159 9 107 191 1 For version with overvoltage protection value 8 mm 2 For version without local display value 10 mm 3...

Page 36: ...3 60 47 3 23 4 222 8 246 2 94 5 16 5 65 45 25 2 107 3 60 47 3 32 4 232 3 264 7 94 5 27 6 65 64 40 2 107 3 60 47 3 41 5 240 8 282 3 94 5 42 65 82 50 107 3 60 47 3 46 5 247 8 294 3 94 5 53 5 65 92 80 10...

Page 37: ...092 1 PN 10 1 4404 316 316L DN mm Centering diameter mm D11 D2 2 s mm 15 54 3 D2 2 0 25 74 3 D1 3 5 40 95 3 D1 5 3 50 110 0 D2 6 8 80 145 3 D2 10 1 100 165 3 D2 13 3 150 221 0 D2 20 0 1 The ow conditi...

Page 38: ...DN mm Centering diameter mm D11 D2 2 s mm 15 54 3 D2 2 0 25 74 3 D1 3 5 40 95 3 D1 5 3 50 110 0 D2 6 8 80 145 3 D2 10 1 100 171 3 D1 13 3 150 227 0 D2 20 0 1 The ow conditioner is tted at the outer di...

Page 39: ...16L DN mm Centering diameter mm D11 D2 2 s mm 15 56 5 D1 2 0 25 74 3 D1 3 5 40 97 7 D2 5 3 50 113 0 D1 6 8 80 151 3 D1 10 1 100 182 6 D1 13 3 150 252 0 D1 20 0 1 The ow conditioner is tted at the oute...

Page 40: ...2501 PN 10 16 25 40 ASME B16 5 Class 150 300 Schedule 40 JIS B2220 10 20K Schedule 40 1 4404 F316 F316L DN A 1 B C1 D E 2 F 2 G H K Di L 3 M in in in in in in in in in in in in in 5 52 2 04 3 48 0 92...

Page 41: ...Q Q F T A0033796 A 1 B C1 F 2 G3 Q T 3 in in in in in in in 5 52 2 04 3 48 10 6 3 4 21 7 52 1 For version with overvoltage protection value 0 31 in 2 For version without local display value 0 39 in 3...

Page 42: ...E F G K Di L 1 M in in in in in in in in in in in 4 22 2 36 1 86 0 92 8 77 9 69 3 72 0 65 2 56 1 77 1 4 22 2 36 1 86 1 28 9 15 10 4 3 72 1 09 2 56 2 52 1 4 22 2 36 1 86 1 63 9 48 11 1 3 72 1 65 2 56...

Page 43: ...The ow conditioner is tted at the outer diameter between the bolts 2 The ow conditioner is tted at the indentations between the bolts Used in combination with anges according to ASME B16 5 Class 300 1...

Page 44: ...um coated compact 15 3 1 25 3 3 40 3 9 50 4 2 80 5 6 100 6 6 150 9 1 Weight in US units DN in Weight lbs Auminum coated compact 6 9 1 7 4 1 8 7 2 9 4 3 12 4 4 14 6 6 20 2 Transmitter remote version Wa...

Page 45: ...Weight in SI units DN mm Weight kg Aluminum coated remote 15 2 1 25 2 3 40 2 9 50 3 2 80 4 6 100 5 6 150 8 1 Weight in US units DN in Weight lbs Aluminum coated remote 4 5 1 5 0 1 6 3 2 7 0 3 10 0 4...

Page 46: ...0 16 PN 25 40 6 3 7 8 1 EN DIN DN1 mm Pressure rating Weight kg 15 Class 150 Class 300 0 03 0 04 25 Class 150 Class 300 0 1 40 Class 150 Class 300 0 3 50 Class 150 Class 300 0 5 80 Class 150 Class 300...

Page 47: ...i s u o h r e t t i m s n a r T s l a i r e t a M Compact version Aluminum AlSi10Mg coated Window material glass Remote version Aluminum AlSi10Mg coated Window material glass Cable entries cable gland...

Page 48: ...as wet on the DSC sensor ange Stainless steel 1 4404 and 316 and 316L Compliant with NACE MR0175 ISO 15156 2015 NACE MR0103 ISO 17945 2015 Parts not in contact with medium Stainless steel 1 4301 304...

Page 49: ...ice data and the event logbook No need to recon gure E cient diagnostics increase measurement availability Troubleshooting measures can be called up via the device and in the operating tools Diverse s...

Page 50: ...ol This communication interface is available in device versions with a HART output 1 10 2 3 4 5 7 6 9 8 A0028746 Fig 21 Options for remote operation via HART protocol passive 1 Control system e g PLC...

Page 51: ...ices not bearing this marking PED are designed and manufactured according to good engineering practice They meet the requirements of Article 4 paragraph 3 of the Pressure Equipment Directive 2014 68 E...

Page 52: ...Measuring device Documentation code EF200 C 172 65765 Operating Instructions Measuring device Documentation code EF200W C 172 65761 Description of Device Parameters Measuring device Documentation cod...

Page 53: ...ed nor does it apply in the following cases 3 Malfunctions due to dirt scale rust etc Malfunctions due to improper installation use handling etc by other than TLV CO LTD authorized service representat...

Page 54: ...Unit 8 137 145 Rooks Road Nunawading Victoria 3131 Australia In East Asia Tel Fax 36 Kaki Bukit Place 02 01 02 Singapore 416214 65 6747 4600 65 6742 0345 Tel Fax Room 5406 No 103 Cao Bao Road Shanghai...