EF200W-C
7
Measuring range
The measuring range is dependent on the nominal diameter, the fluid and environmental influences.
The following specified values are the largest possible flow measuring ranges (Qmin to Qmax)
for each nominal diameter. Depending on the fluid properties and environmental influences,
the measuring range may be subject to additional restrictions. Additional restrictions apply
to both the lower range value and the upper range value.
Flow measuring ranges in SI units
DN
[mm]
Liquids
[m³/h]
Gas/steam
[m³/h]
15
0.06 to 4.9
0.3 to 25
25
0.18 to 15
0.9 to 130
40
0.45 to 37
2.3 to 310
50
0.75 to 62
3.8 to 820
80
1.7 to 140
8.5 to 1
800
100
2.9 to 240
15 to 3
200
150
6.7 to 540
33 to 7
300
Flow measuring ranges in US units
DN
Liquids
Gas/steam
[in]
[ft³/min]
[ft³/min]
½
0.035 to 2.9
0.18 to 15
1
0.11 to 8.8
0.54 to 74
1½
0.27 to 22
1.3 to 180
2
0.44 to 36
2.2 to 480
3
1 to 81
5 to 1
100
4
1.7 to 140
8.7 to 1
900
6
3.9 to 320
20 to 4
300