2

3. All installation restrictions and instructions in the Inducer installation instructions must be adhered to when using the UC1.

4. Make certain power source is adequate for the UC1 and Venter requirements.  Do not add equipment to a circuit when the total 

electrical load is unknown.

UC1 UNIVERSAL CONTROL BOARD FEATURES

# 1.

Power supplied by board.  Do not supply power to this area or control damage may result.

# 2.  Do not supply power to the appliance interlock block with the call selector in the “DRY” position.  

Control damage may result if power is supplied.

# 3.  Circuit protection must be provided by the installer.  16 Amps is the maximum current allowed for this device at terminal L.  

A 15 Amp circuit breaker is recommended.

VETI

I

UC1 LED STATUS & FAULT INDICATORS

LED INDICATOR LIGHTS 

LED #1 (Amber)  Appliance call for heat.
LED #2 (Blue) 

Safety circuit through P1 & P2 (Inducer Fan Prover and/or Limit).  Indicates Inducer prover is closed 
during run cycle. Burner circuit is energized with Interlock Relay contact closure from terminal 3 to 4.  

LED #3 (Green)  Power switched to Inducer motor from L to MTR & M.
LED #4 (Red) 

Status / Fault indicator.

LED #5 (Red)

Used as a status indicator.

LED #6 (Red)

115 VAC power supplied to board.  

APPLIANCE CALL 
VOLTAGE SELECTION

Place 

RED

voltage jumper in

proper location based on
appliance call interlock volt-
age.  

SEE WARNING # 2.

IMPORTANT

LED 1 (AMBER)
LED 2 (BLUE)
LED 3 (GREEN)
LED 4 (RED)
LED 5 (RED)

LED 6 (RED) POWER LED

DRY 

24 V

115 V

APPLIANCE
INTERLOCK

RELAY

INDUCER

MOTOR

RELAY

A B   1   2   3   4   L N 

J1    J2       XL    XN

P1   P2    C   GND   F

(1            9)

N     M    MTR    

J1- J2 CALL 
JUMPER

Used when the call signal is
used as the “proven” return
signal to the appliance.  See
wiring section for details.

L / N - 115 VAC POWER 
SUPPLY BLOCK

115 VAC / 50-60 Hz
Circuit protection provided by installer.

SEE WARNING # 3.

MTR & M / N LOAD TERMINALS 
FROM INDUCER MOTOR RELAY

Used to drive Inducer Motor. 
1 HP MAX LOAD across terminals MTR & M / N.  

XL / XN AUXILIARY DEVICE 
POWER TERMINALS 

115 VAC - Maximum of 0.15 Amps.
Only connect to Tjernlund auxiliary devices.

SEE WARNING # 1.

APPLIANCE INTERLOCK
RELAY

1 HP MAX LOAD across 
terminals 3 & 4.

P1 - P2 SAFETY CIRCUIT
TERMINALS

1 mA @ 5VDC.

SEE WARNING # 1

.

C, GND, F AUXILIARY DEVICE 
COMMUNICATION TERMINALS

2 mA @ 5VDC.  For Tjernlund MAC1E or 
MAC4E auxiliary devices. 

SEE WARNING # 1

.

DIP SWITCH SETTINGS

Pre-Purge (1-2)
Post-Purge (3-8) 
Prover status check (9)
See “Pre / Post Purge &
Prover Status Check Dip
Switch Settings”. 

LED STATUS LIGHTS

See “LED Status & Fault
Indicator Section” for details.

APPLIANCE INTERLOCK 
TERMINAL BLOCK (A-B, 1-4)
A - B

- Dry Contact call. 3 mA @ 5VDC.

SEE WARNING # 1.

1

- 24 or 115 VAC intercepted call.  

IMPORTANT

: RED voltage jumper must 

match intercepted call voltage.

2

- 24V common or 115V Neutral.

3

- Common terminal to appliance relay con-

tacts.  

IMPORTANT:

J1-J2 jumper routes 

call voltage at terminal 1 to 3.  Remove 
J1-J2 jumper if a different voltage source is 
provided to terminal 3.

4

- Normally open terminal of appliance relay.  

Will be energized from terminal 3 if safety 
circuit is “proven”. 

INDUCER MOTOR RELAY

1 HP MAX LOAD from 
terminals L to MTR & M.

Summary of Contents for UCRT

Page 1: ...ESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAM...

Page 2: ...ight carrier and your distributor immediately and file a concealed damage claim INSTALLATION RESTRICTIONS 1 The Pre Cycle Prover Status Check is deactivated from the factory on the UCRT Natural chimne...

Page 3: ...ED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY INDUCER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR J1 J2 CALL JUMPER Used when the call signal is used as the proven return...

Page 4: ...be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault code to clear PRE POST PURGE AND PROVE...

Page 5: ...VOLTAGE SOURCE IS PROVIDED TO TERMINAL 3 120 VAC 10 50 60 Hz MOTOR 1 H P MAX 120 VAC 50 60 Hz USER PROVIDED 24 VAC AT TERMINALS 1 2 1 CALL HOT 2 COMMON CONTROL REQUIRES 5 mA 24 VAC TO TRIGGER MOVE RE...

Page 6: ...ed in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC power is removed the UC1 boa...

Page 7: ...heaters To interlock a millivolt water heater and a 24 115 VAC furnace or boiler add the WHKE and MAC1E MILLIVOLT HEATER INSTALLATIONS Each millivolt appliance interlocked with the UC1 must have its o...

Page 8: ...arity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITI...

Page 9: ...und wires in UCRT to supply ground Important Installer must supply overload and disconnect protection 5 If not previously completed connect Black White and Red leads from UCRT to like colors in Roofto...

Page 10: ...ol goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT PRIMARY CONTROL WITH A LINE VOLT...

Page 11: ...lue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call f...

Page 12: ...to the ground screw in the Rooftop Inducer whip 4x4 weatherproof box Connect Blue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive UC1 UNIVERSAL CONTROL C...

Page 13: ...that a slight positive draft neutral to 0 01 W C or 2 5 Pa is measured at the appliance draft sampling location Flue gases should just start to spill from the draft hood draft diverter or barometric d...

Page 14: ...original position the fault code will be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault...

Page 15: ...4 Red will be reset if the call for heat interlock signal or 115 VAC power is removed If the fan prover makes on start up but breaks for more than 10 seconds during the burner cycle LED 4 will flash...

Page 16: ...ined return it to your Tjernlund distributor for replacement Please include UCRT date code component was taken from The date code is located on the Electrical Box coverplate If the date code is older...