RECOMMENDED DISCHARGE HOOD TERMINATION CLEARANCES
These recommendations are based on the National Fire Protection Association requirements for other sidewall discharge
devices. Always check local codes when installing this unit.
• Discharge should not be installed within 20 feet of another home or directed so as to jeopardize people or enter buildings.
• Discharge should be no less than 7 feet above grade when located adjacent to public walkways.
• Discharge should be no less than 3 feet above any air inlet located within 10 feet.
• Discharge should be at least 4 feet below or 4 feet horizontally from any door or window
• The bottom of the discharge should be located at least 12 inches above grade.
• If possible, do not locate discharge on a wall that faces the direction of the prevailing winds.
FAN INSTALLATION
1. Determine the centerline exit point for the PVC discharge pipe based on the orientation of the surface that the mounting
bracket will be attached to, (See Diagrams A, B, & C). Dimensional diagram on page 2 can also be referenced.
2. Mark centerline and drill small pilot hole to outside to verify that the termination hood is favorably positioned on the
home’s exterior, (See Diagrams D & E).
3. Using a 4" hole saw drill through to exterior.
NOTE:
When hole saw reaches back of siding it may be preferable to finish
cut from outside, (See Diagram F).
4
Diagram A
Diagram B
Diagram C