Setup
Menu Defaults
The tables below detail the default values and the range of available settings, plus any additional information about the
unit's configurable settings.
SETUP1
Configurable Item
Range
Default
Additional information
Min
Max
Time
Any Time
00:00
24 hour clock.
Day of Week
1
7
1
Two groups, five week days & two
weekend days.
Backlight Brightness
Off
4
1
Off, 25%, 50%, 75% & 100%
Boost Overrun
Kitchen
0 mins
60 mins
15 mins
Wet Room 0 mins
60 mins
15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the
aurastat
's fan button to trigger boost.
The
aurastat
's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer
0 mins
60 mins
0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the
aurastat
's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Boost Inhibit On/Off
On
Off
Off
Boost Inhibit Times
Start
00:00
23:59
23:00
End
00:00
23:59
05:00
Internal Humidity Boost
(Setpoint)
30%
89%
70%
SETUP2
Configurable Item
Range
Default
Additional information
Min
Max
Filter Change Interval
3 months
24 months
12 months
Boost Overrun Timer
Kitchen
0 mins
60 mins
15 mins
Wet Room 0 mins
60 mins
15 mins
Boost Overrun timers are set independently for Kitchen and Wet Room inputs.
Boost Overrun timers must be set greater than zero for any momentary switch or the
aurastat
's fan button to trigger boost.
The
aurastat
's fan button uses the Kitchen Boost Overrun timer.
When using latching switches to initiate Boost SPEED 3 the Overrun timer will start when the latching switch is disengaged.
Boost Delay Timer
0 mins
60 mins
0 mins
If the Boost Delay Timer is set greater than zero momentary switches or the
aurastat
's fan button will not switch the HRV into
Boost SPEED 3. When using latching switches, if the Boost switch is turned of before the Boost Delay Timer has elapsed the
HRV will not Boost.
Speed 4 SUMMERboost®
14%
100%
100%
SUMMERboost® is only available on
models with Summer. SUMMERboost®
is disabled by default.
Press and release the + / - key to modify the mantissa(decimal). Press and hold the + / - key to modify the characteristic
(interger). HRV fan speed will change to reflect the displayed setting when the button is released. Changes in fan speed
will take time to be reflected as changes to the ventilation system airflow rates. Fan speed will not change while in this
configuration menu.
Boost Alert On/Off
On
Off
On
Boost Alert Timer
1 hour
10 hours
2 hours
15
Summary of Contents for aurastat VT
Page 1: ...ventilation systems aurastat VT TP534 HRV Controller Product Manual EN ...
Page 25: ...verrun Setup Boost Delay Timer Boost Inhibit On Off Setu Inhi 25 ...
Page 26: ...Setup Boost Inhibit Times Done Setup Internal Humidity Boost Partial SETUP1 2 of 2 26 ...
Page 29: ...verrun Setup Boost Delay Timer Setup Speed 4 SUMMERBoost Boost Alert On Off Setu Boo Time 29 ...
Page 31: ...Summer By Pass Enable Disable Setup Summer By Pass 31 ...
Page 34: ...SETUP2 4 of 4 Setup Internal Humidity Boost Full Done 34 ...
Page 43: ...ted ys Done is available after Day 7 Setup is complete Done 43 ...