24
Configurable Item
Range
Default
Configured
Additional
information
Min
Max
Speed 3, Boost.
Supply
14%
100%
100%*
Extract
14%
100%
100%*
Speed 4, SUMMERboost®
Supply
14%
100%
100%
Extract
14%
100%
100%
Summer Bypass
Extract (From
property)
17°C
35°C
22°C
Supply (From
atmosphere)
10°C
20°C
15°C
In order for the Summer Bypass to operate the temperatures of both the air being extracted from the property and supplied from outside
must be above their individual thresholds. If the temperature of the Supply air is less than 1°C cooler than the Extracted air the Summer
Bypass does not operate to prevent the warmer air being supplied directly to the property. Manual Summer Bypass switches the Summer
Bypass in or out regardless of the measured temperatures.
SUMMERboost®
Enabled
Disabled
Enabled
SUMMERboost® operates in conjunction with Summer Bypass and switches the fans to Speed 4. It can also be disabled by a latching switch
if fitted.
Filter Change Interval
1 month
24
months
6 months
Display Mode
ECO
ON
ECO
Switch Inputs
SW1
SUMMERboost®
Disable
SW2
"Wet Room
Boost"
SW3
Speed 1 Setback
Switch options are: Kitchen Boost, Wet Room Boost, Speed 1, SUMMERboost disable, Speed 4, OFF (normally open), OFF (normally closed),
Manual Summer Bypass and Boost Inhibit.
When configured as Kitchen or Wet room Boost, the switch will use the associated Boost overrun time for that room.
When configured as OFF (normally open) both fans will stop when the switch is closed or if OFF (normally closed) is configured the fans will
stop when the switch is opened.
Some control features documented in this manual may not be compatible with older
Titon HRV units. If you are replacing an older
auralite
controller please check with
technical at Titon to confirm unit is compatible with
aura-t
.