HRV ECO
aura
Defaults
The table below details HRV settings and defaults, which that the
aura-t
CANNOT configure. During installation and
commissioning they may be changed from the default values by an alternate Titon controller. There is space available in
the table where the installer should record configuration settings.
Configurable Item
Range
Default
Min
Max
Boost Delay
Timer
Kitchen
0 mins
60 mins
0 mins
Wet Room
0 mins
60 mins
0 mins
If the Boost Delay Timer is set greater than zero momentary switches will not switch the HRV into Speed 3 Boost. When using latching
switches the HRV will not Boost until the Delay time has elapsed.
Filter Change Interval
3 Months
24 Months
12 Months
Summer Bypass Enable/Disable
Enabled
Disabled
Enabled
Frost Protection Mode
Off
Reduce
Off
Frost Protection Threshold
-2°C
11.5°C
0.5°C
When Frost Protection is operating in Off Mode the Supply fan is switched off when the temperature measured by the sensor on the
to atmosphere side of the heat cell drops below the Frost Protection Threshold.
Duct Heater Enable/Disable
Enabled
Disabled
Enabled
Duct Heater Mode
Frost
User
User
Duct Heater Threshold
-4°C
16°C
3°C
Duct Heater Hysteresis
1°C
10°C
1°C
When operating in Frost Mode the Duct Heater uses the sensor on the to atmosphere side of the Heat Cell and switches on 2°C above
the Frost Protection threshold. When operating in User Mode it uses the sensor on the from atmosphere side of the heat cell and the
threshold and hysteresis detailed above. In both modes the Duct Heater will be switched off if the Supply fan speed drops below
22.5% PWM.
Internal Humidity Boost
On
RH Boost Overrun
1 min
60 mins
15 mins
RH Boost Hysteresis
1%
10%
1%
When the Humidity of the air being extracted from the property reaches the threshold configured by the
aura-t
the fans switch to
Speed 3 Boost. They remain at Speed 3 until the Humidity has dropped below the threshold minus the hysteresis and the RH Boost
Overrun time has elapsed.
Room Sensor 1 Enable/Disable
Enabled
Disabled
Disabled
Sensor Type
%RH
Lower threshold
60%
Upper threshold
70%
Room Sensor 2 Enable/Disable
Enabled
Disabled
Disabled
Sensor Type
CO
2
Lower threshold
800PPM
Upper threshold
1400PPM
If fitted, Room Sensors are used to provide Demand Control Ventilation based on the environmental parameter they are measuring.
Below their lower threshold they have no effect on the ventilation rate; once the lower threshold is exceeded the fan speeds
proportionally increase from Speed 2, Continuous until the upper threshold is reached when the fans will be running at Speed 3,
Boost. In addition to the %RH and CO
2
sensor detailed above Air Quality and Temperature Room Sensors may be fitted. With any
Room Sensor the range of Demand Control Ventilation will be dependant on the individual sensor’s characteristics and the thresholds
configured by the installer.
37