background image

To reset an end device; remove the battery, press and hold the PCB push button down while re-inserting the battery. Once 

the battery is inserted, release the PCB push button

.

Upon resetting, the device will leave its current network, restore the factory default settings for the minimum, maximum 

and delta change reporting along with the polling intervals. Once reset the device will search for strongest HA1.2 and 

attempt to join.

Default and Recommended Settings

:

Setting

Default

Range

Minimum Reporting Interval

60 seconds

0-65536 seconds

Maximum Reporting Interval

300 seconds

0-65536 seconds

Delta Change Reporting Threshold

0.5°C

0-32767 (0-327.67°C)

Polling during normal operation

60 seconds

0-65536 seconds (Polling will match the Min Reporting

Value)

Polling (accelerated) upon joining/re-

joining network

Every 2 seconds for 60 

seconds

N/A

It is possible to force specific features within the sensor by holding the PCB push button and releasing at certain 

points of the LED sequence. To perform one of the below tasks, press and hold the PCB button, the LED will begin 

to flash every second, release at the relevant point of the sequence to perform the associated task.

LED Timing

Feature

Release after 1st LED flash

Sensor reads sensor value and updates clusters

Release after 2nd LED flash

No action

Release after 3rd LED flash

Initiates the OTA update process

Release after 4th LED flash

Factory reset

Supported Clusters & Attributes

The below Server/Client clusters are supported by the TPZDS/HA1.2 temperature sensor:

Sensor Server Clusters

:

Cluster Name

Cluster ID

Cluster Attributes

Basic

0x0000

Application Version 

Stack Version 

Hardware Version 

Manufacturer Name 

Model Identifier 

Date Code 

Software Build Id 
Device Enabled

Power Configuration

0x0001

Battery Voltage 

 

Battery Percent Remaining  
Battery Alarm Mask  
Battery Alarm State  

Battery Voltage Minimum Threshold 

Battery Voltage Threshold 1 

Battery Voltage Threshold 2 

Battery Voltage Threshold 3

Identify

0x0003

Identify time

Commissioning Cluster

0x0015

Extended Pan ID 

Channel Mask 

Start-up control

Temperature Measurement

0x0402

Measure Value 

 

Min Measured Value 

Max Measured Value

Zigbee HA1.2 Wireless Duct Temperature Sensor (TPZDS/HA1.2)

Reviews: