To reset an end device; remove the battery, press and hold the PCB push button down while re-inserting the battery. Once
the battery is inserted, release the PCB push button
.
Upon resetting, the device will leave its current network, restore the factory default settings for the minimum, maximum
and delta change reporting along with the polling intervals. Once reset the device will search for strongest HA1.2 and
attempt to join.
Default and Recommended Settings
:
Setting
Default
Range
Minimum Reporting Interval
60 seconds
0-65536 seconds
Maximum Reporting Interval
300 seconds
0-65536 seconds
Delta Change Reporting Threshold
0.5°C
0-32767 (0-327.67°C)
Polling during normal operation
60 seconds
0-65536 seconds (Polling will match the Min Reporting
Value)
Polling (accelerated) upon joining/re-
joining network
Every 2 seconds for 60
seconds
N/A
It is possible to force specific features within the sensor by holding the PCB push button and releasing at certain
points of the LED sequence. To perform one of the below tasks, press and hold the PCB button, the LED will begin
to flash every second, release at the relevant point of the sequence to perform the associated task.
LED Timing
Feature
Release after 1st LED flash
Sensor reads sensor value and updates clusters
Release after 2nd LED flash
No action
Release after 3rd LED flash
Initiates the OTA update process
Release after 4th LED flash
Factory reset
Supported Clusters & Attributes
:
The below Server/Client clusters are supported by the TPZDS/HA1.2 temperature sensor:
Sensor Server Clusters
:
Cluster Name
Cluster ID
Cluster Attributes
Basic
0x0000
Application Version
Stack Version
Hardware Version
Manufacturer Name
Model Identifier
Date Code
Software Build Id
Device Enabled
Power Configuration
0x0001
Battery Voltage
Battery Percent Remaining
Battery Alarm Mask
Battery Alarm State
Battery Voltage Minimum Threshold
Battery Voltage Threshold 1
Battery Voltage Threshold 2
Battery Voltage Threshold 3
Identify
0x0003
Identify time
Commissioning Cluster
0x0015
Extended Pan ID
Channel Mask
Start-up control
Temperature Measurement
0x0402
Measure Value
Min Measured Value
Max Measured Value