User Manual-MA2T
Version A August 2021
25 of 25
25
configuration again
Symptom
Possible cause
Action
Actuators run in smaller steps
before stopping (Under parallel
configuration)
Insufficient power supply
Check the power supply while the
actuator is running
Connect the actuators to PGMA one
at a time and check the following:
Reason for last stop
Current cut-off levels in both
directions
After everything is connected, supply
power to all actuators at the same
time. Then wait 10 seconds before the
Run In/Run Out signals are activated.
Signal cable damaged or
removed under operation (Under
parallel configuration)
All actuators stop at the same
position
The signal and power cables MUST be
reconnected to all actuators.
Ensure that no actuator is missing in
the system. Otherwise, the system will
not work, not even after re-powering.
Please see the non-critical info below.
After everything is connected, power
on all actuators at the same time.
Then wait 10 seconds before the Run
In/Run Out signals are activated.