Overfill Prevention Controller EUS-2 | 

Technical Description  

 

 

 

 

[email protected] 
www.timm-technology.de  

1.

 

General Information  

As  stationary  part  of  the  Overfill  Preven-
tion System for liquid fuels, the explosion-
proof  control  unit  type  EUS-2  complies 
with the requirements on overfill preven-
tion  systems  for  bottom-loading  tank 
trucks  according  to  Annex  IV  of  VOC-Di-
rective 94/63/EC as well as with European 
standard EN  13922 and  American API RP 
1004  recommendations.  Timm  has  com-
bined  its  longterm  competencies  in  ex-
plosion  protection  and  experiences  in 
overfill  prevention  in  this  control  unit. 
EUS-2 is characterised by ease of installa-
tion,  convenient  operation,  functional 
safety and a user-friendly state-of-the-art 
explosion  protection  concept  (IEPC)  de-
signed by Timm. 

2.

 

Functional Principle 

To ensure a safe filling process, the overfill 
prevention  controller  EUS-2  provides 
three main functions: 

 

Overfill prevention 

 

Grounding verification 

 

Vapour recovery monitoring 

During  loading  of  tank  trucks,  the  level 
sensors at the truck (one sensor per tank 
compartment) are connected to the con-
trol unit at the filling gantry by a standard 
plug  and  socket  connection.  The  level 

sensors are positioned in the top of each 
tank  compartment  deep  enough  to  as-
sure  that  once  a  sensor  gets  activated, 
product  flow  stops  before  the  compart-
ment  is  completely  full.  In  case  a  sensor 
senses liquid, the control unit triggers to 
shut-off the product flow for all compart-
ments  to  prevent  leakage  of  fuel  or  the 
compartment’s bursting. 

When  being  connected  to  a  tank  truck, 
the control unit EUS-2 detects the type of 
level  sensors  (optic/thermistor),  the  sen-
sor installation (five-wire/two-wire) as well 
as  the  way  of  ground  verification  (re-
sistance/ ground bolt) and activates auto-
matically  the  required  operating  mode. 
For  a  wide  range  of  applications,  tank 
trucks with up to twelve five-wire sensors 
and eight two-wire sensors are supported. 
The control unit verifies permanently the 
correct  grounding  of  the  truck  via  the 
connection cable. The preset limit value of 
this verification can be set according to in-
dividual  requirements  exceeding  EN 
13922 requirements. 

The  vapour  recovery  hose  connection  is 
monitored on the tank truck via an elec-
tro-pneumatic  interlock  switch,  which  is 
looped  into  the  grounding  verification 
line.  The  control  unit  EUS-2  ensures  that 
filling is only possible if the vapour recov-
ery  system  and  the  grounding  line  are 
connected properly. 

Figure 1: Bottom loading with overfill prevention control by Timm`s control unit type EUS-2

 

Summary of Contents for EUS-2

Page 1: ...H Timm Elektronik GmbH Humboldtstr 29 21509 Glinde GERMANY OVERFILL PREVENTION CONTROLLER EUS 2 Technical Description Version 1 81 English...

Page 2: ...n Protection 2 3 3 High Functional Safety Fail Behavior 2 3 4 Bright Signal Light 2 3 5 Graphic Display 2 3 6 Easy Configuration by Joystick 3 3 7 Reliable Ground Verification 3 3 8 Control Outputs Da...

Page 3: ...nnection The level sensors are positioned in the top of each tank compartment deep enough to as sure that once a sensor gets activated product flow stops before the compart ment is completely full In...

Page 4: ...With this unique combination of the types of protection the main housing can be opened in gas hazardous areas when power is switched on for configuration and service e g for setting the additional co...

Page 5: ...e plug and socket connection will be noticed in time for pre ventive measures 3 8 Control Outputs Data Interface Six control outputs enable advanced op tions for connecting the control unit ac cording...

Page 6: ...systems Blue marked plug with three lock ing pins and seven electrical con tacts fitting onto 6 pin truck sock ets for optic vehicle sensor systems acc to API RP 1004 standard The additional 7th pin...

Page 7: ...onal truck socket for detecting the truck connector in park position status by integrated socket code generator 4 3 Testing Equipment The functioning of the control unit can easily get checked by usin...

Page 8: ...functional limitations must be ob served Maximum values Uo 12 7 V Io 129 mA Po 360 mW 5 3 Control Output Circuits Contact Outputs Type of protection Increased safety Ex eb Maximum values 250 V AC 3 A...

Page 9: ...ower supply 1 2 Closing contact output K1 Filling release 3 4 Closing contact output K2 Filling release 5 7 Switching contact output K3 Configurable 8 10 Switching contact output K4 Configurable 15 16...

Page 10: ...s In addition to the ATEX certificate we also have Ex approvals for the EUS 2 according to IECEx and EAC Ex according to TR CU 012 2011 for Australia Oceania and the Eurasian cus toms union Europe EU...

Page 11: ...es or technical support our employees will be glad to be available for you on the following contact information Dr Alexander Zelck Head of international sales 49 40 248 35 63 31 zelck timm technology...