6. Installation

•  The RCD should form part of a 30A ring main or 

terminate a spur off a 30A ring main. The cable 
connecting the supply to the RCD should be either:  
2x 2.5mm² for the ring main or 1x 2.5mm for the spur.

•  Make sure to tighten all screw terminals onto  

exposed wires.

•  Ensure that there is both sufficient length of the supply 

cable tails(s) to enable easy wiring.

  Note: With some makes of BS4662 boxes it will be 

necessary to bend back the upper and lower fixing lugs 
to enable RCD to be fitted.

6.1  Ensure the mains supply is switched off and the circuit 

supply fuses are removed or the circuit breaker turned off.

6.2  Connect the incoming 230V 50Hz supply and outgoing 

load cables to the relevant terminals ensuring correct 
polarity is observed and that all bare conductors are 
sleeved (see section 7. Connection Diagram).

6.3  Finally secure the unit to the back box with the fixing 

screws provided, forming the cables during installation 
to avoid any entrapment and cable damage.  
Do not over tighten.

Summary of Contents for RCD05WAVN

Page 1: ...p e r a t i n g I n s t r u c t i o n s RCD Double Sockets RCD05WAVN RCD Double White Socket Active RCD06WPVN RCD Double White Socket Passive RCD07MAVN RCD Double Metal Socket Active RCD08MPVN RCD Do...

Page 2: ...Device 2 Safety Before installation or maintenance ensure the mains supply to the RCD fused connection unit is switched off and the circuit supply fuses are removed or the circuit breaker turned off...

Page 3: ...ric pollution A warming of the casing during use is normal Do NOT use outside the service conditions For devices having a solid neutral ensure the correct polarity of the incoming supply connections s...

Page 4: ...ed Trip Current 30mA RCD Type Double Pole suitable for 2 and 3 wire applications Breaking Capacity 250A Earth leakage Through Fault Withstand 1500A Operating Temp Range 5 C to 40 C Trip Speed Less tha...

Page 5: ...sion if set will retain closed contacts if the mains supply is interrupted essential for applications such as freezers The non latching version if set allows the contacts to open if the mains supply i...

Page 6: ...5 RCD05WAVN RCD06WPVN Blue Reset button R for RCD01WAVN Grey Reset button R for RCD02WPVN Status indicator shows Red for ON Green for OFF Red Test T button ON OFF Switches...

Page 7: ...WAVN RCD06WPVN 2x 3 5mm diameter fixing screws 25mm long RCD07MAVN RCD08MPVN 1x Warning label 1x Instruction manual 1x Metal Surface Box RCD07MAVN RCD08MPVN Blue Reset button R for RCD03MAVN Grey Rese...

Page 8: ...boxes it will be necessary to bend back the upper and lower fixing lugs to enable RCD to be fitted 6 1 Ensure the mains supply is switched off and the circuit supply fuses are removed or the circuit b...

Page 9: ...e of the back box entries to secure the gland or conduit The gland or conduit must not project into the back box beyond the lock ring a male adapter should be used within the back box along with a fem...

Page 10: ...hould show Green This indicates the RCD had been tripped and power has been disconnected 8 3 RESET Press the Grey Blue Reset button marked R again the status indicator should show Red If all the above...

Page 11: ...sional advice 3 Year Guarantee In the unlikely event of this product becoming faulty due to defective material or manufacture within 3 years of the date of purchase please return it to your supplier i...

Page 12: ...a product brochure please contact Qualified Customer Support Co ordinators will be on line to assist in resolving your query If you experience problems do not immediately return the unit to the store...