•  Multiple PIR Sensor Switching:  A maximum of 4 PDSM1500 PIR sensors can be  

   

wired in parallel, to enable any detector to turn  

   

ON all the lights connected (The total load must  

   

not exceed the lamp rating of a single  

   

PDSM1500 unit).

4. Selecting a Location

•  Careful positioning of the sensor will be required to ensure optimum 

performance (See diagram “A” & “B” detailing detection range and direction).

•  The best all-around coverage is achieved with the unit mounted at the optimum 

height of 3 metres.

•  The sensor is more sensitive to movement ACROSS its field of vision than to 

movement directly TOWARDS (see diagram “B”). Therefore position the unit  
so that the sensor looks ACROSS the likely approach path.

•  Reflective surfaces (i.e. pools of water or white-painted walls) may cause  

false activation under extreme conditions.

•  During extreme weather conditions the motion sensor may exhibit unusual 

behaviour. This does not indicate a fault with the sensor. Once normal  
weather conditions return, the sensor will resume normal operation.

230V 

50Hz 

Mains 

Supply 

IN

Switched

Load

OUT

230V 

50Hz 

Mains 

Supply 

IN

Switched

Load

OUT

Summary of Contents for PDSM1500

Page 1: ...I n s t a l l a t i o n O p e r a t i n g I n s t r u c t i o n s 360 Surface Mount Ceiling PIR Light Controller Model PDSM1500...

Page 2: ...itted does not exceed the rating of the circuit cable fuse or circuit breaker 3 Technical Specifications 230V AC 50 Hz This PIR is of Class ll Construction and must not be earthed Motion Detection Ran...

Page 3: ...t all around coverage is achieved with the unit mounted at the optimum height of 3 metres The sensor is more sensitive to movement ACROSS its field of vision than to movement directly TOWARDS see diag...

Page 4: ...ad cables into the terminal block ensuring correct polarity is observed and that all bare conductors are sleeved See section 6 Connection Diagram The adjustment knobs located beneath the sensor head s...

Page 5: ...les to the terminal block as follows 230V AC 50Hz Mains Supply Live Brown or Red to L Neutral Blue or Black to N Load Switch Live Brown or Red to L1 Neutral Blue or Black to N L L1 N 230V AC 50Hz MAIN...

Page 6: ...prox 5 seconds each time This allows testing to be carried out to establish whether the sensor is covering the required area Walk across the location the sensor is fitted to establish the detection ar...

Page 7: ...o start operating The setting is best achieved by the procedure below 1 Set the DUSK control knob fully anti clockwise 2 When the ambient light level reaches the level of darkness at which you wish th...

Page 8: ...off at the isolation switch Turn back ON again after 30 seconds Leave for approximately 15 minutes If light activates check area for false activation from heat wind or reflective source Check that the...

Page 9: ...in the area may be too bright to allow operation at the current DUSK setting During the hours of darkness adjust the DUSK control slowly clockwise until the lamp illuminates See section 7 Setting Up...

Page 10: ...proof of purchase and it will be replaced free of charge For years 2 and 3 or any difficulty in the first year telephone the helpline on 020 8450 0515 Note A proof of purchase is required in all cases...

Page 11: ...10...

Page 12: ...csc timeguard com For a product brochure please contact If you experience problems do not immediately return the unit to the store Telephone the Timeguard Customer Helpline Qualified Customer Support...

Reviews: