
46
SHB10 TIKI
Section 9 |
Control
Menu 1.3 - scheduling
In the menu scheduling indoor climate (heating/cool-
ing/ventilation) is scheduled for each weekday. You
can also schedule a longer period during a selected
period (vacation) in menu 4.7.
In menu 1.3, select heating or cooling (if active), then
program the room temperature increase or decrease
for up to three time intervals throughout the day. More
information after selecting "?".
Activated:
Scheduling for the selected period is activat-
ed here. Set times are not affected at deactivation.
System:
Which climate system the schedule is for is
selected here. This alternative is only displayed if more
than one climate system is present.
Day:
Select which day or days of the week the sched-
ule is to apply to here. To remove the scheduling for a
particular day, the time for that day must be reset by
setting the start time to the same as the stop time. If
the line "all" is used, all days in the period are set for
these times.
Time period:
The start and stop time for the selected
day for scheduling are selected here.
Adjustment:
See relevant sub menu.
Conflict:
If two settings conflict with each other a red
exclamation mark is displayed.
Factory setting:
heating: wył.
cooling (if activated): wył.
Menu 1.9 - Advanced
Menu 1.9.1 - curves
This menu is intended for advanced users. This menu
has several sub-menus.
You can select heating or cooling (if active) in the
curve menu. The next menu (heating curve/cooling
curve) shows the heating and cooling curves for
your house. The task of the curve is to give an even
indoor temperature, regardless of the outdoor tem-
perature, and thereby energy efficient operation. It is
from these heat curves that the heat pump’s control
computer determines the temperature of the water
to the system, the supply temperature, and therefore
the indoor temperature. Select the curve and read off
how the supply temperature changes at different out-
door temperatures here. The number to the far right
of "system" displays which system you have selected
the heating curve/cooling curve for.
The optimum slope depends on the climate condi-
tions in your location, if the house has radiators or un-
der floor heating and how well insulated the house is.
The curve is set when the heating installation is in-
stalled, but may need adjusting later. Normally, the
curve will not need further adjustment. More informa-
tion after selecting "?".
The figure at the end of the curve indicates the curve
slope. The figure beside the thermometer gives the
curve offset. Use the control knob to set a new value.
Confirm the new setting by pressing the OK button.
Curve 0 is an own curve created in menu 1.9.7.
Factory setting:
Heating curve: 7
CAUTION
When making fine adjustments of the indoor tempera-
ture, the curve must be offset up or down instead, this
is done in menu 1.1 temperature.
IMPORTANT
Under floor heating systems are normally max flow line
temperature set to between 35 and 45 °C. Must be re-
stricted with underfloor cooling min. flow line temp. to
prevent condensation. Check the max temperature for
your floor with your installer/floor supplier.
Summary of Contents for SHB10
Page 2: ......
Page 87: ......
Page 88: ...TIKI HVAC d o o Partizanska cesta 12 3320 Velenje Email servis tiki si www TIKI si ...