Enable SHOWER Function 

P13 

Enable ANTISEIZE of Pump1 

P14 

Abilitazione ANTISEIZE of Pump2 

P15 

Type of manifold Probe 

P17 

PWM1 Management 

P18 

PWM2 Management 

P19 

Percentage of PWM1 Duty Cycle at  Minimum Speed  HEATING profile 

U01 

85 

100 

Percentage of PWM1 Duty Cycle at Maximum Speed  HEATING profile 

U02 

100 

Percentage of PWM1 Duty Cycle in Antifreeze HEATING profile 

U03 

100 

Percentage of PWM1 Duty Cycle in Safety HEATING profile 

U04 

100 

Percentage of PWM1 Duty Cycle in Antiseize  HEATING profile 

U05 

100 

Percentage of PWM1 Duty Cycle in Manual Mode HEATING profile 

U06 

50 

100 

Percentage of PWM2 Duty Cycle at  Minimum Speed  HEATING profile 

U11 

85 

100 

Percentage of PWM2 Duty Cycle at Maximum Speed  HEATING profile 

U12 

100 

Percentage of PWM2 Duty Cycle in Antifreeze HEATING profile 

U13 

100 

Percentage of PWM2 Duty Cycle in Safety HEATING profile 

U14 

100 

Percentage of PWM2 Duty Cycle in Antiseize HEATING profile 

U15 

100 

Percentage of PWM2 Duty Cycle in Modalità Manual HEATING profile 

U16 

100 

Percentage of PWM2 Duty Cycle at  Minimum Speed  SOLAR profile 

U21 

15 

100 

Percentage of PWM2 Duty Cycle at Maximum Speed  SOLAR profile  

U22 

95 

100 

Percentage of PWM2 Duty Cycle in Antifreeze SOLAR profile  

U23 

100 

100 

Percentage of PWM2 Duty Cycle in Safety SOLAR profile 

U24 

100 

100 

Percentage of PWM2 Duty Cycle in Antiseize SOLAR

 

profile 

U25 

100 

100 

Percentage of PWM2 Duty Cycle in Manual Mode SOLAR profile 

U26 

50 

100 

Hydraulic Plant Configuration 

ConF 

16 

 
 
 

7. 

PLUMBING/HYDRAULIC PLANTS

 

 

Summary of Contents for GLH110

Page 1: ...85 25 C 2 INSTALLATION Make sure that the Main Power Supply is OFF prior to installing the device Install the product in a dry environment with proper climatic conditions Insert a bipolar main switch compliying to local regulations Avoid coupling the probe cables with these of power Use for wiring cables with conductors of appropriate section and in according the rules Position the probes to detec...

Page 2: ...nsor the message Lo appears If the probe reading is above the maximum range of the sensor the message Hi appears SAFETY FEATURE When this function is activated P11 1 it starts a heat disposing process to remove excess heat buildup of the fireplace The management of the safety feature is expalined in the plumbing hydraulic schematic drawing parapraphs ALARM FUNCTION If the temperature measured by S...

Page 3: ...NU Fireplace Probe P01 0 NTC10K P01 1 NTC100K P01 2 PT1000 DHW Boiler Probe Tall Buffer P02 0 NTC10K P02 1 NTC100K P02 2 PT1000 Short Buffer Probe P03 0 NTC10K P03 1 NTC100K P03 2 PT1000 Ambient Probe P04 0 NTC10K P04 1 NTC100K P04 2 PT1000 Manifold Probe P17 0 NTC10K P17 1 NTC100K P17 2 PT1000 S3 INPUT CONFIGURATION Parameter P05 can be enabled to mange the following P05 0 S3 input DISABLED P05 1...

Page 4: ...WM Manual The PWM duty cycle which determines the speed of the pumps is set with the following parameters U06 if PWM1 with Heating profile Fireplace Pump U16 if PWM2 with Heating profile Heating Pump U26 if PWM2 with Solar profile Solar manifold Pump Automatic PWM In relation to the type of pump the PWM duty cycle is calculated on the basis of the temperature of the fireplace probe high Buffer Tan...

Page 5: ... 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Valve Thermostat for DHW priority A24 20 70 90 C Thermostat to activate Integration on Fireplace probe A03 20 45 90 C Thermostat Integration Buffer Tank on High Buffer Tank Probe A19 20 45 90 C Heating Pump Thermostat on Fireplace probe A04 20 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Heating Pump Thermostat on High B...

Page 6: ...esis Thermostat of Integr Buffer Tank on High Buffer Tank Probe IA19 0 2 20 C Hysteresis Thermostat of Buffer Comfort on High Buffer Tank probe IA20 0 2 20 C Hysteresis Thermostat of High Temp on High Buffer Tank probe IA23 0 2 20 C Hysteresis Thermostat of Valve for DHW priority IA24 0 2 20 C Hysteresis Thermostat of Manifold Pump Activation IA33 0 2 20 C Hysteresis Thermostat of ANTIFREEZE Therm...

Page 7: ...ycle at Minimum Speed HEATING profile U11 0 85 100 Percentage of PWM2 Duty Cycle at Maximum Speed HEATING profile U12 0 5 100 Percentage of PWM2 Duty Cycle in Antifreeze HEATING profile U13 0 0 100 Percentage of PWM2 Duty Cycle in Safety HEATING profile U14 0 0 100 Percentage of PWM2 Duty Cycle in Antiseize HEATING profile U15 0 0 100 Percentage of PWM2 Duty Cycle in Modalità Manual HEATING profil...

Page 8: ...F P2 P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 2 ConF 2 Name Symbol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 2 1 Parameters Cod Led Description U Min Def Max A01 Fi...

Page 9: ...A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 4 ConF 4 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 4 1 Pa...

Page 10: ... A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 6 ConF 6 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 6 1 P...

Page 11: ...ON S1 45 A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 8 ConF 8 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Probe Boiler Sanitary DHW S2 15 16 Probe Ambient Thermostat Pressure Sens...

Page 12: ...5 2 e S3 Open o P05 3 e S3 20 b01 OFF S2 45 A19 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 10 ConF 10 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Manifold Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Buffer Probe S2 15 16 Manifold Prob...

Page 13: ... o Shower ON Sanitary DHW OFF OFF S1 80 A07 Safety ON ON S1 45 A02 Sanitary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 12 ConF 12 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 ...

Page 14: ...itary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 14 ConF 14 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 14 1 Parameters Cod Led Description U Min Def Max A01 Fireplace Pump m...

Page 15: ...0 Service ON S3 45 A19 Integration 9 10 Open OFF P3 S3 45 A17 Heating ON P4 Se P06 3 Hydraulic Plant 16 ConF 16 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Buffer Probe Basso S2 15 16 Buffer Probe Alto S3 16 17 7 16 1 Parameters Cod Led Description U Min Def Max A01 Minimum temp P...

Reviews: