TiEmme GLH110 User Manual Download Page 3

 

Pag. 3/15  

0CAR6IN019124_Manual_GLH110_Rev_0.3

 

 

PUMP P1 FUNCTIONING TEST 

When the controller is OFF,  prolongued pressure of  

K3 

key: 

 

 

P1

 output is activated for as long as the key is pressed and the display will show

 tSt1 

 

PUMP P2 FUNCTIONING TEST 

When the controller is OFF,  prolongued pressure of  

K4 

key: 

 

P2/P4

 output is activated for as long as the key is pressed and the display will show

 tSt2 

 

SERVICE OUTPUT 

P4 SERVICE output is programable from the Installer MENU by using parameter 

P06

 

P06 = 0 DISABLED

: the output does not work.

 

 

P06 = 1 THERMOSTAT

: the output is activated if the temperature of 

S1 

probe is above Thermostat 

A09. 

 

P06 = 2 GRILL

: press 

K1

 key to turn on/off the output.

 

 

P06 = 3 AIR DAMPER

: this output is used to manage an Air Damper to adjust for Combustion Air Flow.

 

 

AIR DAMPER 

To make use of the Air Damper function set parameter 

P06 = 3

 

If the output is ON the Air Damper will be Open, if the output OFF the Air Damper will be closed. 

The Air Damper will stay Open as long as the temperature of S1 probe is below 

A05 

Thermostat. The Air Damper will close 

when the temperature is above this Thermostat.

 

 

If 

P12 = 1

 the 

Start Manual

 function is enabled: 

If S1 Temperature is below 

A01

, the Air Damper will Close. During the Ignition phase of the Fireplace, by pressing 

K1 

key 

the  Air  Damper  will  Open  manually  (the  output  corresponding  Led  will  flash).  When  the  Temperature  falls  below 

A01

Thermostat after 

t06

 time the Air Damper will close automatically. 

 

PROBE TYPE 

The controller can manage NTC10K, NTC100K and PT1000 type of probes, which can be configured by using parameters 

P01

P02

P03 

and

 P17

 of the Installer MENU. 

 

Fireplace Probe:  

 

 

P01 = 0 → NTC10K; P01 = 1 → NTC100K; P01 = 2 → PT1000 

 

DHW Boiler Probe/ Tall Buffer :   P02 = 0 → NTC10K; P02 = 1 → NTC100K; P02 = 2 → PT1000 

 

Short Buffer Probe:  

 

P03 = 0 → NTC10K; P03 = 1 → NTC100K; P03 = 2 → PT1000 

 

Ambient Probe: 

 

 

P04 = 0 → NTC10K; P04 = 1 → NTC100K; P04 = 2 → PT1000 

 

Manifold Probe: 

 

 

P17 = 0 → NTC10K; P17 = 1 → NTC100K; P17 = 2 → PT1000 

 

S3 INPUT CONFIGURATION 

Parameter 

P05 

can be enabled to mange the following:

 

 

P05 = 0, S3 

input

 

DISABLED 

 

P05 = 1, S3 

input

 

PRESSURE SENSOR 

 

P05 = 2, S3 

input

 

AMBIENT SENSOR 

 

P05 = 3, S3 

input

 

AMBIENT SENSOR 

 

PRESSURE SENSOR 

If 

P05=1 

pressure sensor management is enabled on probe 

S3

If 

P07=1

 pressure sensor errors are enabled:  

 

If Water Pressure < 

Pr1

 dispaly shows 

PrLo

 + audible signal.

 

 

If Water Pressure > 

Pr2

 dispaly shows 

PrHi

 + audible signal.

 

 

PROBE SENSOR/AMBIENT THERMOSTAT 

Parameter 

P05

 can be setup to enable the management of the Probe Sensor/Ambient Thermostat 

 

If the Ambient Temperature 

S3

>

b01 

or the Ambient Thermostat is 

Open

 (

 

Led flashing

) and there is 

NO

 DHW request 

 

The Shutter is closed 

The  hydraulic/plumbing  plants  with  a  Buffer  tank;  if  the  Ambient  Temperature  is 

S3

>

b01 

or  the  Ambient  Thermostat  is 

Open 

the

 

Heating Pump will be turned off (deactivated) 

 

SHOWER 

 (

P13=1) 

if used in specific hydraulic/plumbing plants where it is required, it can be enabled by pressing 

K2 

key for 3 sec

 

 

 

The display shows 

T03

 time (minutes) giving (DHW) Domestic Hot Water priority;

 

 

 

K3

 and 

K4 

keys increase /decrease the duration 

 

 

Wait 5 seconds to save and exit from this setup. 

 

To exit without saving press 

K1 

key. 

T03 

time is signaled by  

 

led flashing, giving priority to DHW production based on the type of hydraulic/plumbing plant 

in use. 
This function is over when 

 

 

T03 

time has expired.

 

 

By pressing again 

K2 

key 

 

If the temperature of 

S1

 Probe is greater than 

A07

 Safety Thermostat: 

And 

T03=0

, the shower function can be disabled by pressing 

K2 

key.

 

Summary of Contents for GLH110

Page 1: ...85 25 C 2 INSTALLATION Make sure that the Main Power Supply is OFF prior to installing the device Install the product in a dry environment with proper climatic conditions Insert a bipolar main switch compliying to local regulations Avoid coupling the probe cables with these of power Use for wiring cables with conductors of appropriate section and in according the rules Position the probes to detec...

Page 2: ...nsor the message Lo appears If the probe reading is above the maximum range of the sensor the message Hi appears SAFETY FEATURE When this function is activated P11 1 it starts a heat disposing process to remove excess heat buildup of the fireplace The management of the safety feature is expalined in the plumbing hydraulic schematic drawing parapraphs ALARM FUNCTION If the temperature measured by S...

Page 3: ...NU Fireplace Probe P01 0 NTC10K P01 1 NTC100K P01 2 PT1000 DHW Boiler Probe Tall Buffer P02 0 NTC10K P02 1 NTC100K P02 2 PT1000 Short Buffer Probe P03 0 NTC10K P03 1 NTC100K P03 2 PT1000 Ambient Probe P04 0 NTC10K P04 1 NTC100K P04 2 PT1000 Manifold Probe P17 0 NTC10K P17 1 NTC100K P17 2 PT1000 S3 INPUT CONFIGURATION Parameter P05 can be enabled to mange the following P05 0 S3 input DISABLED P05 1...

Page 4: ...WM Manual The PWM duty cycle which determines the speed of the pumps is set with the following parameters U06 if PWM1 with Heating profile Fireplace Pump U16 if PWM2 with Heating profile Heating Pump U26 if PWM2 with Solar profile Solar manifold Pump Automatic PWM In relation to the type of pump the PWM duty cycle is calculated on the basis of the temperature of the fireplace probe high Buffer Tan...

Page 5: ... 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Valve Thermostat for DHW priority A24 20 70 90 C Thermostat to activate Integration on Fireplace probe A03 20 45 90 C Thermostat Integration Buffer Tank on High Buffer Tank Probe A19 20 45 90 C Heating Pump Thermostat on Fireplace probe A04 20 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Heating Pump Thermostat on High B...

Page 6: ...esis Thermostat of Integr Buffer Tank on High Buffer Tank Probe IA19 0 2 20 C Hysteresis Thermostat of Buffer Comfort on High Buffer Tank probe IA20 0 2 20 C Hysteresis Thermostat of High Temp on High Buffer Tank probe IA23 0 2 20 C Hysteresis Thermostat of Valve for DHW priority IA24 0 2 20 C Hysteresis Thermostat of Manifold Pump Activation IA33 0 2 20 C Hysteresis Thermostat of ANTIFREEZE Therm...

Page 7: ...ycle at Minimum Speed HEATING profile U11 0 85 100 Percentage of PWM2 Duty Cycle at Maximum Speed HEATING profile U12 0 5 100 Percentage of PWM2 Duty Cycle in Antifreeze HEATING profile U13 0 0 100 Percentage of PWM2 Duty Cycle in Safety HEATING profile U14 0 0 100 Percentage of PWM2 Duty Cycle in Antiseize HEATING profile U15 0 0 100 Percentage of PWM2 Duty Cycle in Modalità Manual HEATING profil...

Page 8: ...F P2 P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 2 ConF 2 Name Symbol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 2 1 Parameters Cod Led Description U Min Def Max A01 Fi...

Page 9: ...A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 4 ConF 4 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 4 1 Pa...

Page 10: ... A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 6 ConF 6 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 6 1 P...

Page 11: ...ON S1 45 A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 8 ConF 8 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Probe Boiler Sanitary DHW S2 15 16 Probe Ambient Thermostat Pressure Sens...

Page 12: ...5 2 e S3 Open o P05 3 e S3 20 b01 OFF S2 45 A19 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 10 ConF 10 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Manifold Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Buffer Probe S2 15 16 Manifold Prob...

Page 13: ... o Shower ON Sanitary DHW OFF OFF S1 80 A07 Safety ON ON S1 45 A02 Sanitary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 12 ConF 12 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 ...

Page 14: ...itary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 14 ConF 14 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 14 1 Parameters Cod Led Description U Min Def Max A01 Fireplace Pump m...

Page 15: ...0 Service ON S3 45 A19 Integration 9 10 Open OFF P3 S3 45 A17 Heating ON P4 Se P06 3 Hydraulic Plant 16 ConF 16 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Buffer Probe Basso S2 15 16 Buffer Probe Alto S3 16 17 7 16 1 Parameters Cod Led Description U Min Def Max A01 Minimum temp P...

Reviews: