173
NV10P - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
f>>def Enable shrink time
EnTc f>>def
OFF | ON
f>> Shrink time
tcf>>def
s
0.07 ... 10.00 step = 0.01
tcf>>def Activation time
Value
s
1 ... 60 step = 1
Underfrequency - 81U
f< Element
Setpoints
f< Logical block
f<BLK1
OFF | ON
f< Breaker failure
f<BF
OFF | ON
f< Disabling by CB_OPEN
f<disbyCB_
OPEN
OFF | ON
f< Start relays
f<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Trip relays
f<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Start LEDs
f<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f< Trip LEDs
f<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time
81U First threshold defi nite time
State
OFF | ON
Pickup value
fn
0.800 ... 1.000 step = 0.001
f<def Operating time
Value
s
0.05 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Voltage control
f< Control enable
f<&
OFF | ON
f< Controlled by UE>>
f<&UE>>
OFF | ON
f< Controlled by digital input
f<&DIGIN
OFF | ON
f< Controlled by 27V1
f<&27V1
OFF | ON
f< Controlled by 59V2
f<&59V2
OFF | ON
f< Controlled by U<
f<&U<
OFF | ON
f< Controlled by 61850 network no link
f<&rete61850-
KO
OFF | ON
f<& Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 200.0 step = 0.1
f< Control relays
f<&-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f< Control LEDs
f<&-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<< Element
Setpoints
f<< Logical block
f<<BLK1
OFF | ON
f<< Breaker failure
f<<BF
OFF | ON
f< Disabling by f<< start
f<disbyf<<
OFF | ON
f<< Disabling by CB_OPEN
f<<disbyCB_
OPEN
OFF | ON
f<< Start relays
f<<ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<< Trip relays
f<<TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
f<< Start LEDs
f<<ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
f<< Trip LEDs
f<<TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Defi nite time