145
NV10P - Manual - 01 - 2015
APPENDIX
Description
Parameter Unit
Setting range
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN18 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN18 matching (B)
none
Binary input IN19
IN19
Logic
Active-ON | Active-OFF
IN19 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN19 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN19 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN19 matching (B)
none
Binary input IN20
IN20
Logic
Active-ON | Active-OFF
IN20 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN20 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN20 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN20 matching (B)
none
Binary input IN21
IN21
Logic
Active-ON | Active-OFF
IN21 tON
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN21 tOFF
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IN21 matching (A)
Reset LEDs | Set profi le | Fault trigger | Block1
| TCS1 | TCS2 | Trip ProtExt | Reset counters |
Reset CB Monitor | 52a | 52b | Open CB | Close
CB | Remote trip | 74VT ext. | f<-f> Control |
UE>> | 27V1 | 59V2 | U<
IN21 matching (B)
none
Binary input IN22
IN22
Logic
Active-ON | Active-OFF
IN22 tON