Thoreson-McCosh Inc
EDITION 05/07/10
17
IB201001.doc
At this point any value between -
11°F/
-
24°C and
-
40°F/
-
40°C can be entered. Pressing
the enter key will store the valid entry and display:
D e w p o i n t S h i f t O n ?
E n t e r < Y E S > o r < N O >
FIGURE 7.2.2 SHIFT SELECTION
Press YES to turn Dew point shifting on, NO to turn it off. At this point, the alarm setpoint
will be displayed for editing.
SECTION 7.3 SETTING THE DEW POINT ALARM SETPOINT
The user should now enter a value that they would like an alarm condition.
NOTE: If using Dew Point Shift, set the dew point alarm to a more positive value to avoid
false alarms.
D e w p o i n t A l a r m
S e t p t = -
3 0 ° F
N e w = -
_ _ ° F
P r e s s E N T E R
FIGURE 7.3 DEWPOINT ALARM SETPOINT
SECTION 8 OPTIONAL SETPOINTS
SECTION 8.1 CFM
A i r s p e e d = 0 0 C F M
P r e s s R E T U R N
FIGURE 8.1 C.F.M. DISPLAY
Pressing the Optional Setpoints key once will display the current air flow rate if this option
has been installed.