![THOMSON TS 870 Installation, Operating & Service Manual Download Page 53](http://html.mh-extra.com/html/thomson/ts-870/ts-870_installation-operating-and-service-manual_1110071053.webp)
TS 870 Transfer Switch
PM062 REV 11 16/04/19
51
Thomson Power Systems
13. REQUIREMENTS FOR UPSTREAM CIRCUIT PROTECTIVE DEVICES
13.1. WITHSTAND CURRENT RATINGS (
ALL MODELS WITHOUT INTEGRAL
OVERCURRENT PROTECTION OPTION)
BASIC MODEL
MAX.
VOLTA
GE
RATED
CURREN
T (A)
WITHSTAND CURRENT
RATING AMPS (RMS)
1
@240V
@480V
@600V
TS87xA-0100
600
100
65,000
25,000
18,000
TS87xA-0150
600
150
65,000
25,000
18,000
TS87xA-0200
240
200
65,000
N/A
N/A
TS87xA-0250
600
250
65,000
35,000
25,000
TS87xA-0400
600
400
65,000
50,000
35,000
TS87xA-0600
600
600
65,000
50,000
35,000
TS87xA-0800
600
800
65,000
50,000
35,000
TS87A-
1000/1200
600
1000/120
0
65,000
50,000
42,000
1. Standard ratings only are shown. Consult Thomson Power Systems for versions
with higher withstand current ratings.
2. For other model types not shown, contact Thomson Power Systems for further
information.
Summary of Contents for TS 870
Page 2: ......
Page 12: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 10 Thomson Power Systems ...
Page 13: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 11 Thomson Power Systems ...
Page 34: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 32 Thomson Power Systems ...
Page 63: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 61 Thomson Power Systems 18 NOTES ...
Page 74: ......
Page 76: ......