TS 870 Transfer Switch
PM062 REV 11 16/04/19
23
Thomson Power Systems
•
If the transfer switch was transferring power from the generator source to the
utility source and the generator switching device failed to open, an auxiliary trip
relay will trip open the utility power switching device to immediately separate
the two power sources.
If the transfer switch was transferring power from the
utility source to the generator source and the utility switching device failed to
open, an auxiliary trip relay will trip open the generator power switching device
to immediately separate the two power sources.
NOTE:
The maximum time period both sources will remain paralleled under
this failure mode is 200 milliseconds.
•
The original source (i.e. prior to the transfer sequence) will remain on load,
separated from the other source. An alarm light and TSC 900 controller will
indicate a failure condition which must be manually reset before the transfer
switch will re-attempt subsequent transfers. For further information on the TSC
900 features and operation, refer to the separate product instruction manual.
NOTE:
Two alarm contacts are provided for the Closed Transition Failure Mode
(i.e. one for a failed generator power switching device and one for the utility
power switching device. The contacts are for customer use to remotely trip open
upstream devices should an abnormal condition persist.
5. Transfer Fail Alarm (Switching Device Fail to Close): The TSC 900 provides a timer
detect and alarm abnormal operating conditions. Should a power switching device
fail to close for any reason within a 5-minute time period, an alarm light and alarm
relay contact will be activated. For further information on the TSC 900 features and
operation, refer to the separate product instruction manual.
5.3.
DUAL SOURCE ATS
NOTE:
This section applies only to Dual Source configured transfer switches.
ATS may be supplied with the following 3 types of optional Dual Source system configurations:
•
DU
-
Dual Utility ATS
: Used for systems consisting of one ATS connected to two
utilities with at least one source continually energized to the ATS. ATS will
automatically switch to the alternate source upon failure of the preferred source.
•
DPG
-
Dual Prime Gen ATS
: Used for systems consisting of one ATS connected
to two generators with one generator continually energized to the ATS. ATS will
automatically switch to the alternate generator upon failure of the preferred source.
•
DSG
-
Dual Standby Gen ATS (Slave ATS):
Used for systems consisting of two
ATS's in a Master/Slave Configuration. Refer to the following diagram. Only the
Slave ATS is to be ordered and configured with the
DSG option. The Master ATS
is to be ordered as a standard ATS. The Slave ATS will be connected to two
Summary of Contents for TS 870
Page 2: ......
Page 12: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 10 Thomson Power Systems ...
Page 13: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 11 Thomson Power Systems ...
Page 34: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 32 Thomson Power Systems ...
Page 63: ...TS 870 Transfer Switch PM062 REV 11 16 04 19 61 Thomson Power Systems 18 NOTES ...
Page 74: ......
Page 76: ......