Anchoring Notes:
1. Anchoring must be designed according to IBC 2012 or latest version.
2. The anchoring details shown are recommended according to the seismic
certification; design Engineer may use alternate anchors within the scope of IBC.
3. Wall anchors in concrete; use a typical concrete anchor as necessary.
4. Expansion anchors as shown. To be installed according to manufacturer's
recommendation.
5. The 800-1200A NEMA 3R ATS enclosure may be floor/wall mounted or it may be
free standing (floor mounted only); If free standing it must be a minimum of 12"
(305mm) away from pipes, conduits or other obstructions to allow for sway during a
seismic event.