MEC 2 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM056 Rev 6 05/10/15
Thomson Technology
51
9.1.1. READ ONLY MODE
User can view the programmable parameters only and cannot change any
values. The factory default number for the read-only level is one (1).
9.1.2. READ / WRITE MODE
User can view and modify any programming parameter as required. The Factory
default number for the read/write level is two (2).
9.1.3. MASTER READ / WRITE MODE
User can view/modify any programming parameter as well as view/modify the
security password level numbers. Contact THOMSON TECHNOLOGY factory
for master password if required.
To enter the programming mode, follow the procedure as shown:
PROGRAM MENU?
YES
Select the Program Menu by scrolling through the display menus using the
ENTER
pushbutton. When displayed, use the
INCREMENT
pushbutton to select
the YES prompt and push the
ENTER
button.
PASSWORD
0
Use the
INCREMENT
or
DECREMENT
pushbuttons to ramp the displayed
number up or down to the desired password access number. Press the
ENTER
pushbutton when the correct number is displayed.
NOTE:
If an invalid number is entered, programming
access will be denied. To exit the programming
mode, press and hold the
EXIT
pushbutton for
more than two seconds until the display changes.