MEC 2 MICROPROCESSOR ENGINE/GENERATOR CONTROLLER
PM056 Rev 6 05/10/15
Thomson Technology
22
FAULT
NAME
FAULT
ACTION
INPUT
SIGNAL
Over voltage
Shutdown
Generator voltage
Over frequency
Alarm
Generator frequency
Over current
Alarm
Generator current
Under voltage
Shutdown
AC Voltage
Under frequency
Shutdown
AC Frequency
Weak battery
Alarm
Battery voltage
Low battery voltage
Alarm
Battery voltage
High battery voltage
Alarm
Battery voltage
Low engine temperature
Alarm
Engine temperature
High engine temperature #1
Alarm
Engine temperature
High engine temperature
# 2
Shutdown
Engine temperature
Low oil pressure
#1 Alarm
Oil
pressure
Low oil pressure
#2 Shutdown
Oil
pressure
Over speed
Shutdown
Engine speed
Loss of speed signal
Shutdown
Engine speed
All fault circuits may be user field programmed for different control functions
however their designated fault function is not programmable. Refer to the
programming instructions for further information.
4.4.2. GENERATOR AC VOLTAGE
4.4.2.1.GENERATOR UNDER VOLTAGE
The MEC 2 controller provides a 3-phase under voltage sensor for the
generator supply. The under voltage sensor is programmable for type of
fault action (i.e. alarm or shutdown), pickup and dropout voltage setpoints
(i.e. adjustable hysteresis) and transient time delay settings. Refer to the
programming instructions for further information.
4.4.2.2.GENERATOR OVER VOLTAGE
The MEC 2 controller provides a 3-phase over voltage sensor for the
generator supply. The over voltage sensor is programmable for type of
fault action (i.e. alarm or shutdown), pickup and dropout voltage setpoints