TS 910 TRANSFER SWITCH
PM140 REV 0 12/02/09
49
Thomson Technology
Symptom
Possible Causes
Generator does not start up or stop
when it should
- Verify remote engine control panel is set for automatic mode
- Verify engine start wiring is on correct terminals of TSC 9
controller.
- Verify engine start wiring is not loose at transfer switch and/or
at the engine control panel
No time delay when there should be
- Verify time delay setting of the TSC 9 controller
21. REPLACEMENT PARTS
Replacement parts are available for the transfer switch as follows:
NOTE
When ordering replacement parts please provide the following
information:
-Transfer Switch Model code (e.g. TS 910A100A)
-Transfer Switch Serial Number (e.g. MW-022345)
The above information can be found on the transfer switch
equipment rating plate located on the inside of the ATS door.
Component Description
Thomson Technology Part
Number
TSC 9 Service Replacement Controller Board c/w faceplate
TSC9SR
TSC 9 Graphic Overlay
010985
Limit Switch 1 n/o, 1 n/c (all ATS Models)
11069
Utility Power Contactor Solenoid Coil
(100A Mechanism) 120V
11070
Generator Power Contactor Solenoid Coil
(100A Mechanism) 120V
11092
Utility Power Contactor Solenoid Coil
(200A Mechanism) 120V
11071
Generator Power Contactor Solenoid Coil
(200A Mechanism) 120V
11093
Utility/Generator Power Contactor Solenoid Coil
(400A Mechanism) 120V
11072
Manual Handle (100-200A Mechanism)
11073
Manual Handle (400A Mechanism)
11074