18.16. LOAD SHED
Load Shed operation can be configured to three different settings as follows:
1. Disabled
2. Basic
3. kW Load Management
The transfer switch is supplied from the factory with the Load shed disabled. Refer to the
following table for detailed description of load shed operating modes, their application and
settings required on the TSC 9.
Load Shed
Feature
Application
Feature Description
TSC 9 CT
Jumper
Position
TSC 9 kW
Settings
Disabled
(factory default)
Load Shed feature not used for applications
using Genset & ATS which are sized for
whole house load
Load Shed Relay & Status LED Indicator are disabled
None
00
Basic
Basic load shed feature used when Genset
is sized for only partial home load and
requires automatic control to shed selected
non-essential load.
Feature activated when TSC 9 kW setting is
>00 setting
- Load Shed Relay & Status LED Indicator are enabled on
TSC 9 controller
- Load Shed Relay & LED are activated whenever
Generator is On Load and resets when load returns to
utility power
- Normally Closed contact opens during Load shed
condition to open control circuit of connected non-essential
load
None
>00 Setting
kW Load
Management
(feature sold
separately-refer
to associasted
instructions for
furhter details)
kW Load Management Load shed used
when Genset is sized for only partial home
load and requires automatic control to shed
selected non-essential load. Feature
provides added benefit of maximizing
available generator capacity where home
loads vary over time. Requires additional
Current Transformers
- Load Shed Relay & Status LED Indicator are enabled on
TSC 9 Controller
- Load Shed Relay & LED are controlled via CT input
signal (refer to kW load Management sequence of
operation)
- Normally Closed contact opens during Load shed
condition to open control circuit of connected non-essential
load
200A or 400A
CT Position
(100A Model
uses 200A CT)
>00 Setting
to be 95% of
Gen kW
rating
When Load shed operation is required, the load shed output relay contact must be
connected to control an external non-essential load. The output contact is normally closed
and opens when a load shed condition is activated. The output contact is rated for 5A,
240VAC (resistive) maximum. The output contact can be directly connected to control
devices such as air conditioners with thermostat control input.