Pag. 9 Tot 27.
THERMOSALD UPSCR_M_V3
08/2000
REFER TO CHAP. 3.4 - WIRING DIAGRAM
CN2 - 230 V SUPPLY : INTERNAL PROTECTION DEVICE PROVIDED
QF0 - D-TYPE, TWO-POLE CIRCUIT BREAKER OR DELAYED-ACTION FUSE
( 6A 1000 VA TRANSFORMER / 8A 1400 VA TRANSFORMER)
QF1 - C-TYPE, TWO-POLE CIRCUIT BREAKER OR FUSE
( 40A WITH BOARD 10030 SCR uP : RATED I = 30A )
( 63A WITH BOARD 10060 SCR uP :RATED I = 60A )
The recommended specifications are for indication purposes only. Take into consideration the electrical system being used
when examining these specifications.
2.6 BAND RESISTANCE CHART
3 COMMISSIONING
Band length
BEVELLED
Band thickness
BEVELLED
Specific resistance R0
Ω
Ω
Ω
Ω
/ m
3
0.1
2.81
3
0.15
1.95
3
0.2
1.50
3
0.25
1.27
4
0.1
2.37
4
0.15
1.40
4
0.2
1.12
4
0.25
0.96
5
0.2
0.8
6
0.1
1.6
6
0.2
0.72
8
0.1
1.2
8
0.2
0.51
Determining the resistance of the band on the machine ( R )
1 -
Single band :
R = R0 x band length [ m ]
2 -
2 series-connected bands :
R = R0 x band length [ m ] x 2
3 -
2 parallel-connected bands :
R = R0 x band length [ m ] / 2
NOTE : With copper-coated bands, "band length" refers to the portion which is not copper-coated