background image

3

Terminator

TM

 ECM-P-WP

 

INSTALLATION PROCEDURES

The Heat Tracing Specialists

®

8.

 

Mount junction box base on expediter.  
Make sure to align slots to properly 
orient junction box base. Tighten nut 
with Terminator-LN-Tool. If mounting 
horizontally, threaded gland holes must 
face downward.

7.

 

Terminate cable with appropriate PETK 
termination kit. Refer to PETK installation 
instructions. Push excess cable back 
through expediter. Tighten cap securely. 
Tape cable expansion loop to pipe.

4.

 

Position RTD Sensor(s) in grommet. Do 
not pull from the sensor end when routing 
through the expediter assembly. Pull 
sensor from the lead wire portion. 

6.

 

Insert cable into expeditor.  Make 
sure bus connection (HPT and FP 
only) remains outside of expediter.

Note:

 For HPT and FP cable, exchange 

grommet in Terminator with grommet 
provided in PETK-3-ECM.

5.

 

Locate bus connection (HPT and FP only) 
as shown. Cut end of cable at angle to 
aid in piercing grommet. Leave additional 
cable for expansion as needed.

3.

 

Mount expediter to bracket using 
M5 x 8mm screws and M5 lock washers.

2b. 

Mounting Method 2: Secure wall mount 
bracket to mounting surface using 
customer supplied screws, 

fl

 at washers, 

and nuts.

2a. 

Mounting Method 1: Secure wall mount 
bracket to mounting surface using pipe 
band provided with kits.

1. 

Slide appropriate IEK insulation entry 
kit components onto cable.

        RTD

Lead Wire

        RTD

Sensor

Summary of Contents for Terminator ECM-P-WP

Page 1: ...atTracingSpecialists 1725 II 2 GD Ex eb mb ib ib IIC T4 Ex tb IIIC T135 C SIRA 12ATEX5239X IP66 60 C Ta 55 C IECEx SIR 12 0103X Ex eb mb ib ib IIC T4 Ex tb IIIC T135 C PN 27673 Do not open while energ...

Page 2: ...ents dry before and during installation Minimum bending radius of heating cable is 32 mm except HPT is 57 mm and FP is 19 mm Individuals installing these products are responsible for complying with al...

Page 3: ...ssembly Pull sensor from the lead wire portion 6 Insert cable into expeditor Make sure bus connection HPT and FP only remains outside of expediter Note For HPT and FP cable exchange grommet in Termina...

Page 4: ...r u s e a s a nadjustable electronic control module 1725 II 2 GD Ex eb mb ib ib IIC T4 Ex tb IIIC T135 C SIRA 12ATEX5239X IP66 60 C Ta 55 C IECEx SIR 12 0103X Ex eb mb ib ib IIC T4 Ex tb IIIC T135 C P...

Page 5: ...e de calorifuge IEK pour fixer le point de p n tration du ruban chauffant au niveau de la t le de protection du calorifuge Deutsch Terminator ECM P WP Elektronisches Regelmodul INSTALLATIONSANWEISUNG...

Page 6: ...Corte el final del cable en ngulo para facilitar perforar el pasacables Deje cable adicional para la coca de expansi n 6 Inserte el cable en el Expediter Aseg rese que el nodo de conexi n queda fuera...

Page 7: ...abel alleen voor HPT en FP zoals aangegeven Snij het einde van de kabel schuin af om het doorsteken door het doorvoerrubber mogelijk te maken Zorg dat er een extra lus in de kabel aanwezig is 6 Steek...

Page 8: ...Specialists Corporate Headquarters 100 Thermon Dr PO Box 609 San Marcos TX 78667 0609 USA Phone 1 512 396 5801 European Headquarters Boezemweg 25 PO Box 205 2640 AE Pijnacker The Netherlands Phone 31...

Reviews: