Thermostat Installation

1. 

FACTORY INSTALLED - For shipping purposes the 
thermostat well (located at back of unit) has not been 
installed.

2. 

Position thermostat bulb perpendicular to housing 
being careful not to kink the capillary. Slide well over 
bulb and screw into place. Make sure that a minimum 
5 threads engagement is achieved
FIELD INSTALLED KIT - Most Norseman

TM

 XB CE units 

are suitable for field installation of a thermostat kit 

with the operator shaft hole on the front side of the 
unit and plugged with a socket head cap screw. If a 

thermostat is to be field installed, check to verify that 

you have been supplied with the correct thermostat 
kit. Single phase heaters use a single pole thermostat 

as supplied in kit number XTKW04481CE. Three 

phase heaters use a double pole thermostat as 

supplied in kit number XTKW04483CE. Follow the 

instructions supplied with the kit.

C. 

WIRING

1. 

Whenever hazardous materials are present, ensure 

that the terminal housing covers are secure before 
powering the heater.

2. 

Use supply wires suitable for 105°C (221°F).

3. 

Use local approved flameproof entry devices as 

required by the code for hazardous locations.

NOTE:        

The reference pressures are as follows:

 

XB1 : 11.1 BAR

 

XB2 & XB3 : 52.8 BAR

 

Use only flameproof entry devices suitable for 

reference pressure.

4. 

To provide maximum protection each Norseman

TM

 

XB CE heater should be fused individually using the 
nearest standard fuse size which is not less than 120% 
of the expected line current.

5. 

All heaters come factory prewired and ready for direct 
connection to the power supply leads.
5.1  Connect the power leads to terminals marked L 

and N for single phase and L1, L2 & L3 for three 

phase heaters as shown in Figure 8.

5.2  Connect the ground wire to the ground 

connection located in the heater terminal 
housing.

Figure 8 – Wiring diagrams

L

N

L

N

L

N

Summary of Contents for Norseman XB Series

Page 1: ...ormat shown This symbol indicates a potentially hazardous situation which if not avoided can result in personal injury or damage to the equipment This symbol indicates a potentially hazardous situatio...

Page 2: ...A Pre installation 3 B Installation 3 B 1 General Requiprements 3 B 2 Wall Mounting 4 B 3 Floor Mounting 4 B 4 Thermostat Installation 5 C Wiring 5 D Replacement Thermostats 6 E Start up 6 F Maintenan...

Page 3: ...ch depending on the model could weigh up to 45 kg 100 lbs Otherwise use the brackets supplied to stand the heater on the floor 2 Do not recess the Norseman XB CE heater into the wall Use of the bracke...

Page 4: ...d lock washers Figure 4 Figure 4 Attach heater to mounting brackets B 3 Floor Mounting Step 1 Position heater face down on the floor with terminal box towards the wall Figure 5 page 4 Figure 5 Floor m...

Page 5: ...d in kit number XTKW04483CE Follow the instructions supplied with the kit C WIRING 1 Whenever hazardous materials are present ensure that the terminal housing covers are secure before powering the hea...

Page 6: ...E The thermostat temperature range is 18 to 40 C 0 to 100 F with an operating differential of 3 to 4 C 5 to 7 F 2 Install the terminal box cover and tighten securely 3 Check to ensure that all plugs s...

Page 7: ...administration F MAINTENANCE 1 Periodically inspect the heater installation to ensure that all connections fittings plugs screws covers etc are tight and free of corrosion 2 Check the extrusions of th...

Page 8: ...applies to paint finishes except for manufacturing defects apparent within 30 days from the date of installation The Company neither assumes nor authorizes any person to assume for it any other oblig...