3.3.6 SETTING THE 

 TEMPERATURE

Press the 

 key until the 

 selector lamp is illuminated, then press the 

or 

 keys to set the Delta T (minimum 4°C, m20°C).

3.3.7

Setting the Frost Protection temperature / Storage Tank Limit Temperature
Note that the unit must be in PROGRAMMING MODE, (keypad lock disabled)
in order to change both values.

1

To adjust TF, first make sure that the display select indicator is at 

.  Now

press the hidden TF adjust key (see section 3.1 diagram for location of key)
and the current TF value will be displayed, (-30°C to +3°C).

2

Use the 

 

 keys to adjust this value.

3

Press the 

 key to exit and accept the new value.

4

Press the hidden TF adjust key a second time.  The tank safety temperature
will be displayed (+60°C to +90°C).

5

Use the 

 

 keys to adjust this value.

6

Press the  key to exit and accept the new value.
The unit can then be brought out of PROGRAMMING MODE pressing and
holding the select key for eight seconds.  The display selector lamp will cease
to flash as the unit is now in DISPLAY MODE.

3.4

ADDITIONAL FEATURES

3.4.1 MAXIMUM AND MINIMUM RECORD TEMPERATURES

The maximum and minimum Collector and Tank temperatures may be

displayed by pressing and holding the 

 key for 3 seconds.  Ensure that the

 or 

 selector lamp is selected.  The display will show the maximum

temperature reached since the unit was reset.  This may be reset to the

present Collector or Tank temperature by pressing the 

 key whilst viewing

the maximum recorded temperature (while the 

 key is pressed).  To view

the maximum ever recorded temperature, continue to press the 

 key for a

further 8 seconds after the maximum temperature has been read (an “F”
indicates that a sensor fault or temperature above 100°C has occurred in the
unit’s history).
The minimum Collector and Tank temperatures may be displayed in the same

manner only using the 

 key.  To reset proceed as above.

The hysteresis has been increased to ± 2°C.

The pump will switch off if the Tank temperature reaches 90°C and back on
again when the tank temperature drops to 86°C.  As before, the pump will run
if the Collector sensor registers a temperature above 99°C, until the Tank
reaches 90°C.  The tank safety temperature has priority over all other
settings.

Summary of Contents for SMT 100

Page 1: ...SMT 100 SOLAR CONTROLLER www Thermomax com...

Page 2: ...ation 10 3 2 2 Auxiliary operation 10 3 2 3 Frost Protection 11 3 2 4 Storage Tank Limit Temperature 11 3 3 Programming the SMT 100 11 3 3 1 Displaying the Collector temperature 11 3 3 2 Displaying th...

Page 3: ...isplay of tank cylinder temperature Precise pump control for efficient heat collection Auxiliary tank thermostat for heat boosting or re routing excess heat Anti frost over ride for system protection...

Page 4: ...s replaced before turning on the mains supply Ensure that all the connections made are secure If any maintenance work e g installing a new battery is required ensure that the unit is isolated from the...

Page 5: ...table 4 core or 3 core cable according to the diagram shown below As with all PT100 sensor applications a good connection is vital It is therefore recommended that wherever there is any doubt a factor...

Page 6: ...eater current rating than 3A This is illustrated in the diagram below 2 Connect the pump cable to the PUMP terminals of the control unit 3 Connect the neutral N of the auxiliary heater or contactor to...

Page 7: ...terminal of the PUMP relay and the common terminal C of the AUX relay see cascade diagram 2 Connect and see cascade diagram 3 Connect the mains supply to the terminals marked MAINS 4 Connect the eart...

Page 8: ...7 2 3 3 NORMAL AUX HEAT EXTRACTION When TC OFF OFF When TC If TT ON OFF and If TT ON ON Extracting excess heat or diverting excess heat...

Page 9: ...No C0328 2 Example of a solar hot water system gas or oil auxiliary heating Logic as 1 above 3 Example of solar hot water system with two users is the main solar storage tank which has an auxiliary h...

Page 10: ...ST PUMP STATE SELECT INCREASE DECREASE PROTECTION INDICATOR KEY SWITCHES TEMPERATURE ADJUST KEY HIDDEN 3 1 1 DISPLAY SELECT INDICATORS WITH SELECT INDICATOR FLASHING KEYPAD LOCK ENABLED KEYPAD LOCK DI...

Page 11: ...conditions must be satisfied before the pump will run 1 As the sun shines on the collector the collector sensor picks up the rise in temperature while the return sensor remains at the existing tempera...

Page 12: ...lay select indicator will be constantly ON NOT flashing to inform you that the keypad lock is engaged and the SMT 100 unit is in DISPLAY MODE A full stop will also appear on the display to inform the...

Page 13: ...DISPLAY MODE 3 4 ADDITIONAL FEATURES 3 4 1 MAXIMUM AND MINIMUM RECORD TEMPERATURES The maximum and minimum Collector and Tank temperatures may be displayed by pressing and holding the key for 3 secon...

Page 14: ...und and the Display Select Indicator will stop flashing showing that the present settings are fixed and protected and a full stop will appear in the display To unlock the keypad press the key for eigh...

Page 15: ...parameters Keypad will not operate Cause Remedy The keypad Lock is on see Keypad Lock section 3 5 2 Problem One of the sensors is reading F Cause Remedy One of the sensors is either faulty or not prop...

Page 16: ...y 0 5m Return A0740 SX Sensor Extender 10m A6911 SX Sensor Extender 20m A6921 SX Sensor Extender 50m A6951 External relay 16A C0328 CE This product has been tested to the EU EMC 89 336 EEC directive a...

Reviews: