Operating instructions and electrological connection of control panel

 M

aster Boiler

 

BUTTON

 01

BUTTON

 04

BUTTON

 03

BUTTON

 02

LAMP

 02

LAMP

 01

LAMP

 03

LAMP

 04

DISPLAY

 

LAMP

 05

BUTTON

 01:

 

Increases the indication we wish to regulate

.

BUTTON

 02:

 

Decreases the indication we wish to regulate

.

BUTTON

 03:

 

Choose the parameter to regulate it

.

                           

PARAMETERS

t 1 : 

Temperature where the burner stops

.

                                                   d 1 : 

Low hysteresis of the burner temperature t1

.  

                                                   t 2 : 

Temperature where the circulator starts

                                                          The operation of heating  

                                                      

                                                   d 2 : 

Low hysteresis of the circulator temperature t2

                                                   t 3 : 

temperature where the circulator starts the  

                                                          Operation of  hot water and heating  
                                                          simultaneously

  

                                                   d 3 : 

Low hysteresis of the circulator temperature t3

                                                   S t : 

Application

     

BUTTON

 04:

 

Switch

  ON / OFF  

of the boiler

DISPLAY 

shows 

:  

 the temperature of the boiler when it is standing

 

                            - 

Parameters in the programming

                            - 

any damages of the boiler

LAMP

  01:

 

lights when the boiler operates

LAMP

  02:

 

lights when the circulator operates

LAMP

  03:

 

lights when the circuit protection is activated

LAMP

  04:

 

lights when the burner block

LAMP

  05:

 

lights when the boiler is activated

Programming

:

 

Press

 

for

 2’’ 

continiously 

 SET 

to enter the programming. With up and down arrows 

adjust the parameters

To go to the next  parameter press

 SET. 

When you get to sign

 S t  

has finished 

programming

After this procedure, temperature appears again on the display

.  

o

o

Recommended parameter values 

:

 

 

           

t 1 : 72 C        d 1 : 2 C

o

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t 2 : 45 C        d 2 : 2 C

                                                    

o

o

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t 3 : 64 C        d 3 : 2 C

 