Thermocet Apertura series Operating And Installation Instructions Download Page 9

Page.9 

The concentric duct system consists of the following components: ( see page  19 ) 

A.  Concentric pipe.                                 K.   Flat roof flashing aluminium     
B.  Concentric 45° bend.                        L.    Storm collar / rosette 
C.  Wall bracket.                                     M.   Horizontal terminal eccentric 
D.  Not available                                      N.   Lead slope roof flashing 20°- 45° 
E.  Concentric 90° bend.                        O.   Vertical terminal 
F.  Wall band adjustable.                       P.    Slope roof flashing 5°- 30° 
G.  Adjustable length.                              
H.   Flat roof plate.                                    
I.     Locking band                                    
J.    Adjustable roof plate                          

 

Connection options for concentric duct system 
 
· Indirect wall feed-through (See Page 14 Diag. 8 & 9 ). 

Always place a length of X=1 metre vertically onto the appliance, immediately followed by a 90° bend and 
an external horizontal terminal set of Y (min.) length. If required, the horizontal section can be extended to 
2 metres plus horizontal terminal (Y max.). 

See diag. 9

 
 

· Roof feed-through without slope ( see Page 16 diag. 10 ). 

  A direct route without slopes is possible, up to a maximum length of X=12 metres (excluding vertical ter- 
  minal), measured from the connection to the fire. The minimum length is 2 metres. The outlet may occupy 
  any position on the roof surface (either flat or sloping); the flue and combustion air inlet are located in the 
  same pressure area. A restriction sheet iron ( 

See Page 14 diag

.

 7 

) must be fitted for lengths of 3 metres  

  and  longer for all types of  gas. 
   

 
· Roof feed-through with 45° slope ( see Page 16 diag. 11 ). 

  Always fit a length of X=1 metre vertically onto the appliance. After this, the route can be continued with  
  two 45° bends (effective length per bend, 1 metre), until the maximum pipe length of 12 metres is reached 
  (including bends, but excluding vertical terminal). The minimum length is 3 metres. The outlet may oc- 
  cupy any position on the roof surface (either flat or sloping); the flue and combustion air inlet are located 
  in the same pressure area. A restriction sheet iron ( 

See Page 14 diag. 7 

) must be fitted for lengths of 3  

  metres and longer for all types of gas. 

 
· Roof feed-through with 90° slope ( see Page 16 fig. 12 ). 

  Always fit a length of X=1 metre vertically onto the appliance. After this, the route can be continued with 
  two 90° bends (effective length per bend, 2 metres), until the maximum pipe length of 12 metres is 
  reached (including bends, but excluding vertical terminal). The minimum length is 5 metres. The outlet  
  may occupy any position on the roof surface (either flat or sloping); the flue and combustion air inlet are 
  located in the same pressure area. Take account of the fact that the horizontal section of pipe must not ex- 
  ceed Y=2 metres (measured between bends) and also ensure there is sufficient slope. A restriction sheet 
  iron ( 

See Page 14 diag. 7 

) must be fitted for lengths of 3 metres and longer for all types of gas. 

 

Structure of concentric duct system 

 
Installation of indirect horizontal feed-through

 

 

· 

The outlet can also be constructed in the outer wall in a situation with upwards discharge (always 1 metre 

  vertical first). Possible nuisance to the neighbourhood must be taken into account. The Buildings Decree 
  contains the relevant regulations. In addition, ensure that the wind pressure on the outlet is not excessive 
  (e.g. in extremely narrow alleyways), since this can affect the performance of the fire.

 

Summary of Contents for Apertura series

Page 1: ...Page 1 OPERATING AND INSTALLATION INSTRUCTIONS Apertura line...

Page 2: ...tinguishing Warning Maintenance 3 Preparations for installing the Apertura Page 6 4 Installation instructions for the Apertura with concentric duct connection Page 7 General instructions Components of...

Page 3: ...e appliance must be checked by the installer for gas tightness to gas and combustion products and the correct operation of the various components and functions In addition the flue system and the outl...

Page 4: ...but this can also be done by pushing the timer button Setting the required temperature Press the auto button until the display starts to flash Use the high low buttons to set the required tempera ture...

Page 5: ...e settings are adjusted by means of the auto and timer modes press one of the high low buttons in order to see whether the transmit symbol appears in the top left of the display and the green LED on t...

Page 6: ...re extinguishing the appliance completely Now turn knob A1 to the right as far as it will go to position push the knob in and then turn it to position Warning After extinguishing the pilot light wait...

Page 7: ...ead Section 5 Concentric duct system on page 8 before installing the ap pliance in connection with the necessity of fitting the restriction sheet First dismantle Front 11 12 or 13 depending on the ver...

Page 8: ...terial See Page 15 A Position the log set as shown on Page 15 Do this with care since soot may be formed if the log set is wrongly positioned You finally position and fit the glass the glazing beads a...

Page 9: ...tive length per bend 1 metre until the maximum pipe length of 12 metres is reached including bends but excluding vertical terminal The minimum length is 3 metres The outlet may oc cupy any position on...

Page 10: ...allation of the vertical terminal The outlet can be placed at any arbitrary position on the roof surface inlet and outlet in identical pressure areas but must comply with the current regulations Use a...

Page 11: ...ry I3p b I3p b I3p b I3p b I3p b I3p b Country NL SP FR BE DE GB Pre Pressure MBAR 50 30 37 30 37 30 37 30 50 50 37 30 Burner Pressure MBAR 36 29 4 36 29 4 36 29 4 36 29 4 36 29 4 36 29 4 Injection Bo...

Page 12: ...Page 12 1...

Page 13: ...Page 13 5 2 4 3...

Page 14: ...Page 14 G25 G20 30 31 7 49 G25 55 G20 30 31 6...

Page 15: ...Page 15 A...

Page 16: ...Page 16 8 9 10 11 12...

Page 17: ...Page 17...

Page 18: ...Page 18 A E B C F I H G K L J M N O P...

Page 19: ...KET 12965024 12965524 D NOT AVAILABLE E CONCENTRIC BEND 90 12965014 12965514 F WALL BAND ADJUSTABLE 12965026 G ADJUSTABLE LENGHT 250 12965006 H FLAT ROOF PLATE 12965020 12965520 I LOCKING BAND 1296503...

Page 20: ...Page 20...

Page 21: ...liance is fitted with insulated covering one of the following materials should only be used Loose white insulation wool heat resistant to 1000 C Rocktherm 180 012 insulation wool 700 C from Rockwool o...

Page 22: ...ot covered by the guarantee Defects caused by inexpert assembly and or treatment Costs of transport assembly and dismantling Glazing fire gratings refractory stones flue gas baffle plates heat shields...

Reviews: