24
40.020.944 - rev.
05 - 2015
Bio Energy series
English
/i
Fault
Cause
Solution
Action
The flame goes out
directly after ignition.
1
The heater has no volt-
age.
Check the electric connec-
tion.
User
2
There is water or sedi-
ment in the fuel tank.
Clean the tank and the fuel
filter, see fig. 3 (F).
User
3
The fuel pump is not
switched on.
Position the switch to "1", see
fig. 5 (A).
User
4
The viscosity of the fuel
is too high
Heat the fuel (with a maxi-
mum of 50 °C) or dilute it with
diesel oil
User
Check the pump thermostat
and replace if necessary.
Dealer
Check the pump motor.
Dealer
Check the fuel pump for dirt. Dealer
5
The fuel supply pipe is
blocked: The fuel flows
back into the fuel tank
through the return pipe.
Clean the fuel supply pipe,
see fig. 3 (O).
User