39
SCHRADER VALVES (continued)
4. Replace valve core if a leak is indicated, and retest.
5. Replace valve cover.
A. If it is the gasket type, replace with flare seal cap NESLAB
part number 009121.
B. Inspect flare surfaces on the valve and cap. They should
be smooth and free of burrs.
C. Apply one drop of the appropriate refrigeration oil to the
flared surface of the cap to prevent galling. Do Not Over
Oil - it will displace the sealant.
D. Apply only one drop of sealant (Perma-Lok® LM012
recommended - NESLAB partnumber 013002) to the first
thread of the valve and work it around at least half way,
but no more than one complete turn.
E. Hand tighten cap until is seats. Apply two wrenches - one
on the valve body, one on the cap: and tighten ¼ turn only.
DO NOT OVERTIGHTEN!
Summary of Contents for NESLAB HX 150
Page 9: ...9 Troubleshooting Chart Weak cooling ...
Page 10: ...10 Troubleshooting Chart Weak cooling continued ...
Page 11: ...11 Troubleshooting Chart Refrigeration pressures ...
Page 42: ...42 ...
Page 47: ...47 ...
Page 51: ...51 ...